Chapter 6—Motor ProtectionPower Xpert C445 Global Motor Management Relay MN042003EN—October 2016 www.eaton.com 127Current Based Protection ParametersTable 28. Current Based ProtectionsNote1 ABC wiring recommended.FaultCodeDefaultStatusFault Action Motor FLA Delay (Seconds)Protection Action Units Note Min. Max. Default Min. Max. Default19 Thermal Overload Fault Trip Enabled Amps C445MA2P4… 0.3 2.4 0.3 Class 5 Class 40 Class 5C445MA005… 1 5 1C445MA032… 4 32 4C445MA045… 5.6 45 5.6C445MB072… 9 72 9C445MC090… 11 90 11C445MC136… 17 136 17C445...ext ext 800 extFault Warning Disabled % 1 100 90 0 0 07 InstantaneousOvercurrentFault Trip Disabled % FLA 50 400 400 0.001 2 2Fault Warning Disabled % FLA 50 400 400 0.2 5 28 Jam Fault Trip Disabled % FLA 50 400 400 1 60 10Fault Warning Disabled % FLA 50 400 400 0.2 5 220 Stall Fault Trip Disabled % FLA 50 400 200 0 0 014 Undercurrent Fault Trip Disabled % FLA 10 90 50 1 60 20Fault Warning Disabled % FLA 10 90 50 0.2 5 26 Current Unbalance Fault Trip Enabled % 1 60 15 1 60 15Fault Warning Disabled % 1 60 15 0.2 5 210 Phase Loss Fault Trip Enabled % 60 60 60 2 2 24 Ground Fault (earth) Fault Trip Enabled Amps C445MA2P4… 0.12 2.4 1 1 60 5C445MA005… 0.25 5 3C445MA032… 1 1 9.6 3C445MA045… 1 1 13.5 3C445MB072… 3 1 21.6 3C445MC090… 3 27 3C445MC136… 34 40.8 34C445...ext 30% ofCTPrimary50% ofCTPrimary50% of CTPrimary