Chapter 5—System Configuration and OperationPower Xpert C445 Global Motor Management Relay MN042003EN—October 2016 www.eaton.com 85Figure 95. 120 Vac Inputs and 120/230 Vac Outputs/C445 PowerNotes:1. The inputs on the Base Control Module are only used bythis Operation Mode if Fieldwire is selected for one ofthe control sources. If Fieldwire is not the Local orRemote control source, all 4 inputs may be used asgeneral purpose inputs.2. No outputs may be used as general purpose outputs forthis Operation Mode.3. If Fieldwire is the Local control source, Input 3 is theRemote input. When power is applied to Input 3, theC445 will be in Remote mode.4. If Fieldwire is the Remote control source and 2-wirecontrol (default) is selected, Inputs 2 and 3 are unusedby this operation mode.5. If 3-wire control is selected along with Fieldwire foreither control source, Input 2 is Permissive.6. Fusing: Although C445 product listings do not requirefusing on the high impedance line voltage measurementinputs, it may be necessary to provide overcurrentprotection of the supply leads in accordance withapplicable final installation specific local, state andnational electrical codes.RESETREMOTERUNCH1T1 T2V1 V2 V3C445M...I1 I2C445BA-SA...CH1CH2CH1I3 I4 IC Q1 Q1 Q2 Q2 Q3 C Q3C D0 D1CH2L2L3PEL1Optional ModbusQ1PE N LIC ICMOTOR3~Q11LINE Q12DELTAPTCQ13STAR123456Q11 Q12Q13Q13Q12(+) Us(-) Us120/240 VAC(+) Uc(-) Uc120 VACFB1FERRITEC445U…