Appendix C—Optional Communication Cards180 Power Xpert C445 Global Motor Management Relay MN042003EN—October 2016 www.eaton.comObject DetailsTable 89. Identity Object—Class 0x01 (1)Class ServicesID Service0x0E Get_Attribute_Single0x01 Get_Attribute_AllInstance ServicesID Service0x01 Get_Attributes_All0x05 Reset ResetService data: 0 Soft Reset: Initializes adapter to the Power-up state.Service data: 1 Factory Reset: Writes default values to all instance attributes and then saves all non-volatile attributes to NVmemory and then performs the equivalent of a Reset (0).0x0E Get_Attribute_SingleClass AttributesSr. No. ID Access Rule Data Type Description Remarks / Default Values1 1 (0x1) Get UINT Revision 12 2 (0x2) Get UINT Max Instances 13 3 (0x3) Get UINT Number of instances 14 6 (0x6) Get UINT Maximum ID Class Attribute 75 7 (0x7) Get UINT Maximum ID Instance Attribute 7Instance AttributesSr. No. ID Access Rule Data Type Description1 1 (0x1) Get UINT Vendor ID 0x44 (68) (Eaton Vendor ID)2 2 (0x2) Get UINT Device Type Motor Starter Profile: 0x163 3 (0x3) Get UINT Product Code 0x830A4 4 (0x4) Get STRUCT of: RevisionUSINT Major Revision 1USINT Minor Revision 15 5 (0x5) Get WORD Status Status will be as per CIP Specification.6 6 (0x6) Get UDINT Serial Number Unique number will be written during production.7 7 (0x7) Get SHORT_STRING Product Name C445 EtherNet Communication Card