Appendix D—Modbus Register Map252 Power Xpert C445 Global Motor Management Relay MN042003EN—October 2016 www.eaton.com716 Q2 Function Select UINT16 RW NVDefault: 55EnumConfig CRCRun LockAdmin LockUSB LockBackup MemOutput Function Select for General Purpose Output 2. Available when thisoutput is not used by the Operation Mode. Default = none, If used by theApplication Mode = Reserved. A soft reset is required after modifying thisparameter, continued.Table 127. C445 Modbus Register Map, continuedRegister Name Attribute DescriptionValue Description18 Tripped Status Bits - Instantaneous over current19 Tripped Status Bits - Current unbalance20 Tripped Status Bits - Current phase loss21 Tripped Status Bits - Residual ground fault22 Motor Control Status - Motor at speed23 Motor Control Status - Ready24 Motor Control Status - Inhibited25 Motor Control Status - Warning26 Motor Control Status - Faulted27 Motor Control Status - Remote enabled28 Motor Control Status - Running 229 Motor Control Status - Running 130 Warning Status Bits - PTC31 Warning Status Bits - Phase rotation mismatch32 Warning Status Bits - Stall33 Warning Status Bits - Overload34 Warning Status Bits - Starts limit exceeded35 Warning Status Bits - Low power36 Warning Status Bits - High power37 Warning Status Bits - Under current38 Warning Status Bits - Frequency deviation slow39 Warning Status Bits - Frequency deviation fast40 Warning Status Bits - Voltage unbalance41 Warning Status Bits - Voltage phase loss42 Warning Status Bits - Power factor deviation43 Warning Status Bits - Jam44 Warning Status Bits - Instantaneous over current45 Warning Status Bits - Current unbalance46 Warning Status Bits - Current phase loss47 Warning Status Bits - Residual ground fault48 Warning Status Bits - External ground fault49 Warning Status Bits - Over voltage50 Warning Status Bits - Under voltage51 Tripped Status Bits - Under voltage52 Tripped Status Bits - Over voltage53 Tripped Status Bits - External ground fault54 Base Control Module Field Output control word - Bit 055 Base Control Module Field Output control word - Bit 156 Base Control Module Field Output control word - Bit 257 Base Control Module Field Output control word - Bit 365535 Reserved