Basic Programming 5 - 2F7 Basic Programming Parameters Description of Parameter TablesThis chapter details all of the parameters in the Quick Setting Menu (-QUICK-). Some parameters are not available for allControl Methods. See Appendix A for details. Setting range and factory default value of the parameter follows the controlmethod table for each parameter. Control Method A1-02 Control Method SelectionThe setting of parameter A1-02 determines which control method the Drive will use for operation. Select the control methodbest suited for the application:V/F Control is for general purpose and multiple motor applications.V/F with PG Feedback is for general purpose applications requiring closed loop speed control.Open Loop Vector is for applications requiring precise speed control, quick response, and higher torque at low speeds(150% torque below 1Hz).Flux Vector Control is for applications requiring very precise speed and torque control at a wide speed range including zerospeed. It requires encoder feedback.Setting Description0 V/F Control (factory default)1 V/F with PG Feedback2 Open Loop Vector3 Flux Vector