Parameters A - 22Digital InputsH1-01Multi-Function Digital InputTerminal S3Function SelectionTerminal S3 SelSelects the function of terminals S3 to S8.0: 3-wire controlFWD/REV selection for 3-wire sequence.1: Local/Remote SelectionClosed = Local, Open = Remote.2: Option/Inv SelectionSelects source of frequency reference and sequence.Closed = Option Card, Open = b1-01 & b1-02.3: Multi-Step Frequency Reference 1Based on status of Multi-Step Reference 1 to 4 (d1-16).4: Multi-Step Frequency Reference 2Based on status of Multi-Step Reference 1 to 4 (d1-16).5: Multi-Step Frequency Reference 3Based on status of Multi-Step Reference 1 to 4 (d1-16).6: Jog Frequency ReferenceClosed = frequency reference from d1-177: Accel/Decel Time Se1ection 1Based on status of Accel/Decel Time Selection 1 and 2.8: External BaseBlock N.O.Closed = Output transistors forced off.Open = Normal operation.9: External BaseBlock N.C.Closed = Normal operation.Open = Output transistors forced off.A: Acc/Dec Ramp HoldClosed = Acceleration suspended and speed held.B: External Overheat Alarm (OH2)Closed = OH2 alarm.C: Terminal A2 EnableClosed = Terminal A2 is active.Open = Terminal A2 is disabled.D: V/F Control with PG DisabledClosed = Speed feedback control disabled.E: ASR Integral ResetClosed = Integral reset.F: Terminal Not UsedTerminal closure has no effect.10: MOP IncreaseClosed = frequency reference increases.Open = frequency reference held.Must be set in conjunction with MOP Decrease and b1-01 mustbe set to 1.11: MOP DecreaseClosed = frequency reference decreases.Open = frequency reference held.Must be set in conjunction with MOP Increase and b1-01 mustbe set to 1.12: Forward JogClosed = Drive runs forward at frequency reference enteredinto parameter d1-17.13: Reverse JogClosed = Drive runs in reverse at frequency reference enteredinto parameter d1-17.14: Fault ResetClosed = Resets the Drive after the fault and the run commandhave been removed.(Continued on following page).0 to 78 24 A A A AH1-02Multi-Function Digital InputTerminal S4Function SelectionTerminal S4 Sel0 to 78 14 A A A ADenotes that parameter can be changed when the Drive is running.Table A.1 F7 Parameter List (Continued)ParameterNo.Parameter NameDigital Operator Display Description SettingRangeFactorySettingControl MethodV/F V/Fw/PGOpenLoopVectorFluxVector