Parameters A - 5Sequenceb1-01Frequency ReferenceSelectionReference SourceSelects the frequency reference input source.0: Operator - Digital preset speed U1-01 or d1-01 to d1-17.1: Terminals - Analog input terminal A1 (or terminal A2 based onparameter H3-09).2: Serial Com - Modbus RS-422/485 terminals R+, R-, S+, and S-.3: Option PCB - Option board connected on 2CN.4: Pulse Input (Terminal RP)0 to 4 1 Q Q Q Qb1-02 Run Command SelectionRun SourceSelects the run command input source.0: Operator - RUN and STOP keys on Digital Operator.1: Terminals - Contact closure on terminals S1 or S2.2: Serial Com - Modbus RS-422/485 terminals R+, R-, S+, and S-.3: Option PCB - Option board connected on 2CN.0 to 3 1 Q Q Q Qb1-03Stopping MethodSelectionStopping MethodSelects the stopping method when the run command is removed.0: Ramp to Stop1: Coast to Stop2: DC Injection to Stop3: Coast with Timer (A new run command is ignored if receivedbefore the timer expires).0 to 3 0 Q Q Q Qb1-04Reverse OperationSelectionReverse OperDetermines the forward rotation of the motor, and if reverseoperation is disabled.0: Reverse Enabled1: Reverse Disabled2: Exchange Phase - Change direction of forward motor rotation.0 to 2 0 A - (A*) A - (A*)b1-05Minimum OutputFrequency (E1-09) or LessOperation SelectionZero-Speed OperOperation method when frequency reference is less than minimumoutput frequency set in E1-09.0: Operates according to frequency reference (E1-09 is disabled)1: Output shuts off (coast to stop if less than E1-09)2: Operates according to E1-09 (frequency reference set to E1-09)3: Zero speed (frequency reference of zero is less than E1-09)0 to 3 0 - - - Ab1-06 Digital Input Scan TimeCntl Input ScansSets the scan rate of terminals S1 to S8.0: 2ms - 2 scans (for quick response)1: 5ms - 2 scans (for noisy environments)0 to 1 1 A A A Ab1-07Local/Remote RunSelectionLOC/REM RUN Sel0: Cycle External RUN - If the run command is closed whenswitching from local mode to remote mode, the Drive will notrun.1: Accept External RUN - If the run command is closed whenswitching from local mode to remote mode, the Drive WILL run.0 to 1 0 A A A Ab1-08Run Command SelectionDuring ProgramRUN CMD at PRG0: Disabled - Run command accepted only in the operation menu.1: Enabled - Run command accepted in all menus (except whenb1-02 = 0).0 to 1 0 A A A ADC Injection Brakingb2-01DC Injection Braking StartFrequencyDCInj Start FreqSets the frequency at which DC injection braking starts when rampto stop (b1-03 = 0) is selected. If b2-01< E1-09, DC Injectionbraking starts at E1-09.0.0 to10.0 0.5Hz A A A Ab2-02DC Injection BrakingCurrentDCInj CurrentSets the DC injection braking current as a percentage of the Driverated current. 0 to 100 50% A A A -b2-03DC Injection Braking Time atStartDCInj Time @StartSets the time of DC injection braking at start in units of 0.01seconds.0.00 to10.00 0.00sec A A A Ab2-04DC Injection Braking Time atStopDCInj Time @StopSets the time length of DC injection braking at stop in units of 0.01seconds.1.When b1-03 = 2, actual DC Injection time is calculated asfollows: b2-04 * 10 * Output Frequency / E1-04.2.When b1-03 = 0, this parameter determines the amount of timeDC Injection is applied to the motor at the end of the decel ramp.3.This should be set to a minimum of 0.50 seconds when usingHSB. This will activate DC injection during the final portion ofHSB and help ensure that the motor stops completely.0.00 to10.00 0.00sec A A A Ab2-08Magnetic FluxCompensation CapacityField CompSets the magnetic flux compensation as a percentage of the no-loadcurrent value (E2-03). 0 to 1000 0% - - A -Denotes that parameter can be changed when the Drive is running.* For parameter b1-04 settings 0 and 1.Table A.1 F7 Parameter List (Continued)ParameterNo.Parameter NameDigital Operator Display Description SettingRangeFactorySettingControl MethodV/F V/Fw/PGOpenLoopVectorFluxVector