Basic Programming 5 - 21 Analog Output Gain H4-02 Terminal FM GainSetting Range: 0.0 to 1000.0Factory Default: 100.0% H4-05 Terminal AM GainSetting Range: 0.0 to 1000.0Factory Default: 50.0%These parameters set the gains for the analog output terminals FM and AM. The analog outputs are used for externalmonitoring of Drive conditions, such as output frequency, output current, PID feedback, and others. To obtain the output level,multiply the monitor output level by the gain set in H4-02 or H4-05.For example, if H4-02=150%, then the FM analog output will output 10Vdc when the assigned output function reaches the 67%level. The analog output has a maximum of 10Vdc.Fig 5.10 Analog Output Gain Setting ExampleOutput Function Level (%)Analog Output Level0 67 10010V x 150%10V