Parameters A - 21F5-08DO-08 Channel 8 OutputSelectionDO Ch8 SelectSets the digital output function number for channel 8. See the H2parameter group for possible selections.Effective when digital output card DO-02 or DO-08 is used.0 to 38 F A A A AF5-09DO-08 Output ModeSelectionDO-08 SelectionSets the function of the DO-08 digital output option board.0: 8-channel individual outputs.1: Binary code output.2: 8-channel Selected - Output according to F5-01 to F5-08settings.0 to 2 0 A A A ACommunications Option SetupF6-01Operation Selection afterCommunication ErrorComm Bus Flt SelSelects the stopping method for a communication option board fault(BUS). Active only when a communication option board is installedand b1-01 or b1-02 = 3.0: Ramp to Stop1: Coast to Stop2: Fast-Stop3: Alarm Only0 to 3 1 A A A AF6-02Selection of External Faultfrom Communication OptionBoardEF0 DetectionSelects the condition in which an EF0 fault is detected from acommunication option board. Active only when a communicationoption board is installed and b1-01 or b1-02 = 3.0: Always detected1: Detected only during operation0 to 1 0 A A A AF6-03Stopping Method forExternal Fault fromCommunication Option BoardEF0 Fault ActionSelects the stopping method for an external fault from acommunication option board (EF0). Active only when acommunication option board is installed and b1-01 or b1-02 = 3.0: Ramp to Stop1: Coast to Stop2: Fast-Stop3: Alarm Only0 to 3 1 A A A AF6-04Trace Sampling fromCommunications OptionBoardTrace Sample TimSets the sample trace for the CP-916 option board. 0 to60000 0 A A A AF6-05Current Monitor Display UnitSelectionCurrent Unit SelSelects the current monitor scaling when using a communicationoption board.0: Displayed in Amps1: 100%/8192 (12 bit binary number with 8192=100% Drive’s ratedcurrent)0 to 1 0 A A A AF6-06Torque Reference/TorqueLimit Selection fromCommunications OptionTorq Ref/Lmt SelSelects torque reference/limit when using communications optionboard.0: Disabled -Torque reference/limit from option board disabled1: Enabled -Torque reference/limit from option board enabled.0 to 1 0 - - - ADenotes that parameter can be changed when the Drive is running.Table A.1 F7 Parameter List (Continued)ParameterNo.Parameter NameDigital Operator Display Description SettingRangeFactorySettingControl MethodV/F V/Fw/PGOpenLoopVectorFluxVector