Parameters A - 29H4-02Terminal FM Gain SettingTerminal FM Gain Sets terminal FM output level when selected monitor is at 100%. 0.0 to1000.0 100.0% Q Q Q QH4-03Terminal FM Bias SettingTerminal FM Bias Sets terminal FM output level when selected monitor is at 0%. –110.0 to110.0 0.0% A A A AH4-04Terminal AM MonitorSelectionTerminal AM SelSelects which monitor will be the output on terminals AM and FC.Same function choices as H4-01. 1 to 45 3 A A A AH4-05Terminal AM Gain SettingTerminal AM GainSets terminal AM output voltage (in percent of 10Vdc) whenselected monitor is at 100% output.0.0 to1000.0 50.0% Q Q Q QH4-06Terminal AM Bias SettingTerminal AM BiasSets terminal AM output voltage (in percent of 10Vdc) whenselected monitor is at 0% output.–110.0 to110.0 0.0% A A A AH4-07Terminal FM Signal LevelSelectionFM Level Select 1Selects the signal level of terminal FM.0: 0 to 10Vdc1: -10 to +10Vdc2: 4 to 20mA*0 or 2 0 A A A AH4-08Terminal AM Signal LevelSelectionAM Level Select 2Selects the signal level of terminal AM.0: 0 to 10Vdc1: -10 to +10Vdc2: 4 to 20mA*0 or 2 0 A A A ASerial Communications SetupH5-01 Drive Node AddressSerial Comm AdrSelects Drive station node number (address) for Modbus terminalsR+, R-, S+, S-. The Drive’s power must be cycled for the setting totake effect.0 to 20Hex 1F A A A AH5-02Communication SpeedSelectionSerial Baud RateSelects the baud rate for Modbus terminals R+, R-, S+ and S-. TheDrive’s power must be cycled for the setting to take effect.0: 1200 bps1: 2400 bps2: 4800 bps3: 9600 bps4: 19200 bps0 to 4 3 A A A AH5-03Communication ParitySelectionSerial Com SelSelects the communication parity for Modbus terminals R+, R-, S+and S-. The Drive’s power must be cycled for the setting to takeeffect.0: No Parity1: Even Parity2: Odd Parity0 to 2 0 A A A AH5-04Stopping Method AfterCommunication ErrorSerial Fault SelSelects the stopping method when a communication timeout fault(CE) is detected.0: Ramp to Stop1: Coast to Stop2: Fast-Stop3: Alarm Only0 to 3 3 A A A AH5-05Communication FaultDetection SelectionSerial Flt DtctEnables or disables the communications timeout fault (CE).0: Disabled - A communication loss will not cause acommunication fault.1: Enabled - If communication is lost for more than 2 seconds, a CEfault will occur.0 to 1 1 A A A AH5-06 Drive Transmit Wait TimeTransmit WaitTIMSet the delay time from when the Drive receives data to when theDrive sends data. 5 to 65 5ms A A A AH5-07 RTS Control SelectionRTS Control SelEnables or disables “request to send” (RTS) control:0: Disabled - RTS is always on1: Enabled - RTS turns on only when sending0 to 1 1 A A A AH5-10<3021>Unit Selection forMEMOBUS Register 0025HMEMOBUS 25H UNITSelects the units used for MEMOBUS registry 0025H (monitors theoutput voltage reference).0: 0.1 V units1: 1 V units0, 1 0 A A A APulse I/O SetupH6-01Terminal RP Pulse Train InputFunction SelectionPulse Input SelSelects the function of pulse train terminal RP.0: Frequency reference1: PID feedback value2: PID setpoint value0 to 2 0 A A A AH6-02Pulse Train Input ScalingPulse In ScalingSets the number of pulses (in Hz) that is equal to the maximumoutput frequency E1-04.1000 to32000 1440Hz A A A AH6-03Pulse Train Input GainPulse Input GainSets the output level when the pulse train input is at 100% as apercentage of maximum output frequency E1-04.0.0 to1000.0 100.0% A A A ADenotes that parameter can be changed when the Drive is running.Note: Some digital outputs are control method dependent.Table A.1 F7 Parameter List (Continued)ParameterNo.Parameter NameDigital Operator Display Description SettingRangeFactorySettingControl MethodV/F V/Fw/PGOpenLoopVectorFluxVector