Digital Operator 3 - 14Use and keys to scroll through the “Auto-Tuning” parameter list. Depending on the Control Method (A1-02)setting, only certain Auto-Tuning parameters will be accessible. See table below.After setting Auto-Tuning parameters according to motor nameplate specifications, press so that the following screenappears on the Digital Operator.Press the RUN key on the Digital Operator to start Auto-Tuning. The motor will automatically run. During this process themotor parameters will be automatically set in the Drive according to the measured values.Table 3.13 Auto-Tuning Parameter ListAuto-Tuning Parameters Control MethodV/F V/F w/PG OLV Flux VectorT1-01 Tuning Mode Selection O O O OT1-02 Motor Rated Power O O O OT1-03 Rated Voltage X X O OT1-04 Rated Current O O O OT1-05 Rated Frequency X X O OT1-06 Number of Poles X X O OT1-07 Rated Speed X X O OT1-08 PG Pulses/Rev X X X OO = Accessible-A.TUNE- RdyAuto-Tuning- - - - - - - - - - - - - - - - - - - - - - - - - - - - -0Hz/ 0.00ATuning Ready ?Press RUN key