Basic Programming 5 - 11 Preset Reference d1-01 Frequency Reference 1 d1-02 Frequency Reference 2 d1-03 Frequency Reference 3 d1-04 Frequency Reference 4Setting Range: 0.0 to E1-04 (Maximum Output Frequency)Factory Default: 0.0Hz d1-17 Jog ReferenceSetting Range: 0.0 to E1-04 (Maximum Output Frequency)Factory Default: 6.0HzUp to 17 preset references (including Jog Reference) can be set through multi-function inputs S3 to S8. The first 4 presetreferences and Jog Reference are accessible through the Quick Setting menu. It is a two-step process to set the Drive up forpreset speeds. First, d1-01 through d1-04 and d1-17 must be programmed with the desired preset speeds and the desired jogspeed, respectively. Next, three of the Drive’s digital inputs need to be programmed and wired as Multi-step Speed Reference1, Multi-step Speed Reference 2, and Jog Frequency.As shown in the above table, it is possible to use analog inputs in place of Frequency Reference 1 and Frequency Reference 2. If b1-01 = 1, then the analog input A1 will be used instead of Frequency Reference 1 for the first preset speed. If b1-01=0then Frequency Reference 1 (d1-01) will be used. If H3-05 = 2, then the analog input A2 will be used instead of Frequency Reference 2 (d1-02) for the second preset speed.If H3-05 ≠ 2, then Frequency Reference 2 will be used.Table 5.2 Preset SpeedPreset SpeedTerminalprogrammedas Multi-stepReference 1Terminalprogrammedas Multi-stepReference 2Terminalprogrammedas JogReferenceDetails1 OFF OFF OFF Frequency Reference 1 (d1-01) or analog input A12 ON OFF OFF Frequency Reference 2 (d1-02) or analog input A33 OFF ON OFF Frequency Reference 3 (d1-03)4 ON ON OFF Frequency Reference 4 (d1-04)5 - - ON* Jog Frequency (d1-17)* The Jog Frequency input is given priority over the multi-step speeds.IMPORTANT The programming of d1-01 through d1-17 will be in the units specified by the display scaling parameter (o1-03).