Communications D - 130019HAlarm content 1Bit 0 Undervoltage (UV)Bit 1 Overvoltage (OV)Bit 2 Heatsink overtemperature (OH)Bit 3 Drive overheat fault (OH1)Bit 4 Overtorque 1 detection (OL3)Bit 5 Overtorque 2 detection (OL4)Bit 6 2-wire sequence input (EF)Bit 7 External Baseblock (BB)Bit 8 External fault 3 (EF3)Bit 9 External fault 4 (EF4)Bit A External fault 5 (EF5)Bit B External fault 6 (EF6)Bit C External fault 7 (EF7)Bit D External fault 8 (EF8)Bit E Cooling fan (FAN)Bit F Overspeed (OS)001AHAlarm content 2Bit 0 Speed deviation (DEV)Bit 1 PG open (PGO)Bit 2 Operator disconnected (OPR)Bit 3 Modbus communication (CE)Bit 4 Bus error (BUS)Bit 5 Waiting for transmission (CALL)Bit 6 Motor overload (OL1)Bit 7 Drive overload (OL2)Bit 8 SI-R/G alarm (E-15)Bit 9 External fault (EF0)Bits A to F Not used001BH Not used001CH Not used001DH Not used001FH Not used0020HDrive statusBit 0 Operation: Operating = 1 Stopped = 0Bit 1 Reverse operation: Reverse operation 0: Forward operationBit 2 Drive start-up complete: Completed = 1 Not completed = 0Bit 3 Fault: Fault = 1Bit 4 Data setting error: Error = 1Bit 5 Multi-function digital output 1 (terminal M1 - M2): ON = 1 OFF = 0Bit 6 Multi-function digital output 2 (terminal M3 - M4): ON = 1 OFF = 0Bit 7 Multi-function digital output 3 (terminal M5 - M6): ON = 1 OFF = 0Bits 8 to F Not usedNote: Communication error details are stored until an error reset is input (errors can be reset while the Drive is operating).Note: Write 0 to all unused bits. Do not write data to reserved or “Not Used” registers and bits.Table D.5 Monitor Data (Continued)Register No. Contents