Basic Programming 5 - 17Table 5.4 V/F Pattern for Drive Capacity F7U22P2 - 2045 for 200V ClassParameterNo. Name Unit Factory SettingE1-03 V/F Pattern Selection — 0 1 2 3 4 5 6 7E1-04 Max. Output Frequency Hz 50.0 60.0 60.0 72.0 50.0 50.0 60.0 60.0E1-05 Max. Output Voltage V 230.0 230.0 230.0 230.0 230.0 230.0 230.0 230.0E1-06 Base Frequency Hz 50.0 60.0 50.0 60.0 50.0 50.0 60.0 60.0E1-07 Mid. Output Frequency V 2.5 3.0 3.0 3.0 25.0 25.0 30.0 30.0E1-08 Mid. Output Voltage V 16.1 16.1 16.1 16.1 40.2 57.5 40.2 57.5E1-09 Min. Output Frequency Hz 1.3 1.5 1.5 1.5 1.3 1.3 1.5 1.5E1-10 Min. Output Voltage V 8.0 8.0 8.0 8.0 6.9 8.0 6.9 8.01. For 400V class units, the voltage values are twice that of 200V class units.2. These default values are for V/F or V/F with PG control methods (A1-02 = 0 or 1)Table 5.4 V/F Pattern for Drive Capacity F7U22P2 - 2045 for 200V Class (continued)ParameterNo. Name Unit Factory SettingE1-03 V/F Pattern Selection — 8 9 A B C D E F &FFE1-04 Max. Output Frequency Hz 50.0 50.0 60.0 60.0 90.0 120.0 180.0 60.0E1-05 Max. Output Voltage V 230.0 230.0 230.0 230.0 230.0 230.0 230.0 230.0E1-06 Base Frequency Hz 50.0 50.0 60.0 60.0 60.0 60.0 60.0 60.0E1-07 Mid. Output Frequency V 2.5 2.5 3.0 3.0 3.0 3.0 3.0 3.0E1-08 Mid. Output Voltage V 20.7 26.4 20.7 26.4 16.1 16.1 16.1 16.1E1-09 Min. Output Frequency Hz 1.3 1.3 1.5 1.5 1.5 1.5 1.5 1.5E1-10 Min. Output Voltage V 10.3 12.6 10.3 14.9 8.0 8.0 8.0 8.01. For 400V class units, the voltage values are twice that of 200V class units.2. These default values are for V/F or V/F with PG control methods (A1-02 = 0 or 1)