Digital Operator 3 - 5 REMOTE Reference (REF) IndicatorThe status of the “REMOTE” Reference (REF) indicator is shown in Table 3.4. This indicator is always “Off” when the Driveis in the “LOCAL” mode. When the Drive is in the “REMOTE” mode, the REF indicator status is dependent on the setting ofparameter b1-01 (Frequency Reference Selection). See Table 3.4. Run IndicatorThe status of the “RUN” indicator is shown in Table 3.5 when the Drive is in either the “LOCAL” or “REMOTE” mode. Stop IndicatorThe status of the “STOP” indicator is shown in Table 3.6 when the Drive is in either the “LOCAL” or “REMOTE” mode.Table 3.4 REMOTE Reference (REF) IndicatorIndicator Status ConditionOnParameter b1-01 (Frequency Reference Selection) is set to terminal strip, communications, optionboard, or pulse train as indicated below:b1-01=1 (Terminals)=2 (Communications)=3 (Option PCB)=4 (Pulse Train)OffParameter b1-01 (Frequency Reference Selection) is set to digitaloperator as indicated below:b1-01=0 (Operator)Table 3.5 RUN IndicatorIndicator Status ConditionOn Drive is running.Blinking Drive is decelerating to a stop.Off Drive is stopped.Table 3.6 STOP IndicatorIndicator Status ConditionOn Drive is decelerating to a stop or stopped.BlinkingDrive is in a run condition but the frequency reference is less than theminimum output frequency E1-09, or the Drive is running in “REMOTE” mode and the “STOP”key on has been pressed.Off Drive is running.