12. Faults12.3 Event12.3 EventEvent Explanation RemedyThe ACTUAL values are notbeing stored retentively.Retention has not been switched on. Switch on retention in theSYSTEM menu.The RETENTION… menu isnot displayed in the SYSTEMmenu.easyE4 device is in RUN operating mode. Select STOP modeThe retentive data is clearedwhen there is a mode changefrom RUN to STOP.This behavior only occurs when using thePW02 (pulse width modulation) functionblock in easyE4.Avoid using the PW02 functionblock.The SYSTEM menu is not dis-played.The device model does not feature this menu. Change easyE4 device if you needretentionWhen the device is switchedon, the easyE4 switches toSTOP modeNo circuit diagram in the easyE4 device Load, input circuit diagramRUN START is deactivated at easyE4. Activating RUN mode in MenuSYSTEM OPTIONS.The contacts of the BC (datablock comparison) and BT(block transfer) functionblocks flash in the powerflow displayThe display of the easyE4 is being updated tointermediate states too frequently althoughthe contacts are operating properlyIgnore this section of the powerflow display.The display is not showinganythingNo supply voltage Switch on the power supplyeasyE4 device faulty Press the OK button. If no menuappears, replace the easyE4device.Text displayed with too many spaces Enter text or do not activate textoutput570 easyE4 11/18 MN050009 EN www.eaton.com