4.2 European Standards196 YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical ManualA - Grounding surface (remove anypaint or sealant)B - Enclosure panelC - Metal plateD - DriveE - Shielded wireF - MotorG - Motor cableH - Cable clampI - Ground wireFigure 4.6 Install a drive with a built-in EMC filter5. Connect a DC reactor to reduce harmonic distortion. Refer to DC Reactor on page 202 for details.Note:• Install a DC reactor specified in this manual for compliance with IEC/EN 61000-3-2 for drive models 2004, 2006, 4002, or4004.• The terminal blocks are different between the drive and the DC reactor. The drive has European type terminal blocks, andthe DC reactor has screw type terminal blocks. Correctly prepare the ends of the wiring.Ground WiringWARNING! Electrical Shock Hazard. Do not remove covers or touch the circuit boards while the power is on. Failure to complycould cause death or serious injury.WARNING! Electrical Shock Hazard. Ensure that the neutral point on the power supply of this product (model number 2xxxB/C,4xxxA/B/C) is grounded for compliance with the EMC Directive before EMC filter is switched ON or if there is high resistancegrounding. Failure to comply could cause death or serious injury.