Parameter Details1111.11 o: Keypad-Related SettingsYASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual 909If a drive is replaced, make sure to set o4-07 = 0 and reset the value of U4-06. When the setting of o4-07 ischanged, the recount of U4-06 starts in accordance with the setting of o4-07. Once the configuration is complete,the setting value of o4-07 automatically resets to 0.Note:The maintenance period differs depending on the environment in which the drive is used.■ o4-09: IGBT Maintenance SettingNo.(Hex.) Name Description Default Setting(Setting Range)o4-09(0525)IGBT MaintenanceSetting U4-07 [IGBT Maintenance] monitor values can be overwritten.0%(0 - 150%)If a drive is replaced, make sure to set o4-09 = 0 and reset the value of U4-07. When the setting of o4-09 ischanged, the recount of U4-07 starts in accordance with the setting of o4-09. Once the configuration is complete,the setting value of o4-09 automatically resets to 0.Note:The maintenance period differs depending on the environment in which the drive is used.■ o4-11: U2, U3 InitializationNo.(Hex.) Name Description Default Setting(Setting Range)o4-11(0510)U2, U3 InitializationResets the records of Monitors U2-xx [Fault Trace] and U3-xx [FaultHistory].0(0, 1)Note:The records for U2-xx and U3-xx are not reset even after initializing the drive with A1-03 [Initialize Parameters].0 : No ResetRetains the records of Monitors U2-xx and U3-xx.1 : ResetResets the records for Monitors U2-xx and U3-xx. After the reset, the setting value of o4-11 is automatically resetto 0.■ o4-12: kWh Monitor InitializationNo.(Hex.) Name Description Default Setting(Setting Range)o4-12(0512)kWh MonitorInitialization Resets the monitor values for U4-10 [kWh, Lower 4 Digits] and U4-11[kWh, Upper 5 Digits].0(0, 1)Note:The values of U4-10 and U4-11 are not reset even after initializing the drive with A1-03 [Initialize Parameters].0 : No ResetRetains the monitor values for U4-10 and U4-11.1 : ResetResets the monitor values for U4-10 and U4-11. After the reset, the setting value of o4-12 is automatically reset to0.■ o4-13: NumOfRunCommands Counter InitialNo.(Hex.) Name Description Default Setting(Setting Range)o4-13(0528)NumOfRunCommands Counter Initial Resets the monitor values for U4-02 [Num of Run Commands], U4-24 [Noof Travels(L)], and U4-25 [No of Travels(H)].0(0, 1)0 : No ResetRetains the monitor values for U4-02, U4-24, and U4-25.V/f CL-V/f OLV CLV AOLV OLV/PMOLV/PM AOLV/PM CLV/PM EZOLVV/f CL-V/f OLV CLV AOLV OLV/PMOLV/PM AOLV/PM CLV/PM EZOLVV/f CL-V/f OLV CLV AOLV OLV/PMOLV/PM AOLV/PM CLV/PM EZOLVV/f CL-V/f OLV CLV AOLV OLV/PMOLV/PM AOLV/PM CLV/PM EZOLV