Parameter List1010.10 H: Terminal FunctionsYASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual 447Setting Function Description Ref.1B Program LockoutThe following parameter setting values can be changed when the terminal set forprogram lockout is ON. When the terminal is OFF, the setting values of parameterscannot be changed.ON : Program LockoutOFF : Parameter Write Prohibit7651E Reference samplehold The analog frequency reference input via terminal A1, A2 or A3 will be sampled andoperation will continue at that frequency.76520 to 2F External faultSelects the drive operation that was active at the time the failure or fault was detected inthe external device connected to the drive from any of the patterns between 20 to 2F.76630 PID integral resetResets the value of the PID control integral to 0 while the terminal is ON, and holds thevalue.76631 PID integral holdThis function force holds the integral value of the PID control as long as the terminal isON.76732 Multi-Step SpeedReference 4 Switches d1-09 to d1-16 [Reference 9 to 16] using a combination of multi-step speedreferences 1, 2 and 3.76734 PID soft startercancel Enables or disables the PID soft starter.ON : DisabledOFF : Enabled76735 PID input levelselection Switches the PID input level (polarity) by turning the terminal on and off.7673E PID SetpointSelection 1 It is used in combination with PID Setpoint Selection 2 [H1-xx = 3F]. Switches the PIDsetpoint to b5-58 to b5-60 [PID setpoint2 to 4].7673F PID SetpointSelection 2 It is used in combination with PID Setpoint Selection 1 [H1-xx = 3E]. Switches the PIDsetpoint to b5-58 to b5-60 [PID setpoint2 to 4].76740 Forward RunCommand (2-WireSeq) Inputs the Forward run command for 2-wire sequence 1. Use it paired with the ReverseRun Command (2-Wire Seq) [H1-xx = 41].ON : Forward RunOFF : Run StopNote:• When the both Forward run command and Reverse run command terminals havebeen turned ON, the drive detects EF [FWD/REV Run Command Input Error](minor fault), and the motor ramps to stop.• The Forward run/Reverse run command is set to terminals S1 and S2 when the driveis initialized using a 2-wire sequence.• Simultaneous use with H1-xx = 42, 43 [Run Command/FWD/REV Command (2-Wire Seq 2)] is not possible.76841 Reverse RunCommand (2-WireSeq) Inputs the Reverse run command for 2-wire sequence 1. Use it paired with the ForwardRun Command (2-Wire Seq) [H1-xx = 40].ON : Reverse RunOFF : Run StopNote:• When the both Forward run command and Reverse run command terminals havebeen turned ON, the drive detects EF [FWD/REV Run Command Input Error](minor fault), and the motor ramps to stop.• The Reverse run command is set to terminal S2 when the drive is initialized using a2-wire sequence.• Simultaneous use with H1-xx = 42, 43 [Run Command/FWD/REV Command (2-Wire Seq 2)] is not possible.768V/f CL-V/f OLV CLV AOLV OLV/PMOLV/PM AOLV/PM CLV/PM EZOLVV/f CL-V/f OLV CLV AOLV OLV/PMOLV/PM AOLV/PM CLV/PM EZOLVV/f CL-V/f OLV CLV AOLV OLV/PMOLV/PM AOLV/PM CLV/PM EZOLVV/f CL-V/f OLV CLV AOLV OLV/PMOLV/PM AOLV/PM CLV/PM EZOLVV/f CL-V/f OLV CLV AOLV OLV/PMOLV/PM AOLV/PM CLV/PM EZOLVV/f CL-V/f OLV CLV AOLV OLV/PMOLV/PM AOLV/PM CLV/PM EZOLVV/f CL-V/f OLV CLV AOLV OLV/PMOLV/PM AOLV/PM CLV/PM EZOLVV/f CL-V/f OLV CLV AOLV OLV/PMOLV/PM AOLV/PM CLV/PM EZOLVV/f CL-V/f OLV CLV AOLV OLV/PMOLV/PM AOLV/PM CLV/PM EZOLVV/f CL-V/f OLV CLV AOLV OLV/PMOLV/PM AOLV/PM CLV/PM EZOLVV/f CL-V/f OLV CLV AOLV OLV/PMOLV/PM AOLV/PM CLV/PM EZOLVV/f CL-V/f OLV CLV AOLV OLV/PMOLV/PM AOLV/PM CLV/PM EZOLV