11.12 T: Auto-Tuning924 YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual■T4-05: Motor Rated FrequencyNo.(Hex.) Name Description Default Setting(Range)T4-05(3134)Motor RatedFrequency Sets the motor rated frequency (Hz).Determined by E9-01and o2-04(40.0 - 120.0 Hz)Note:When set to T4-02 = 1, 2 [Motor Type Selection = PM (permanent magnet), SynRM (synchronous reluctance)], input can be skippedsince the following is assumed: Motor Rated Revolutions/60 × Number of Motor Poles/2.■T4-06: Motor Rated VoltageNo.(Hex.) Name Description Default Setting(Range)T4-06(3135)Motor Rated VoltageSets the rated voltage (V) of the motor.200 V Class: 200.0 V,400 V Class: 400.0 V(200 V Class: 0.0 -255.0 V, 400 V Class:0.0 - 510.0 V)■T4-07: Motor Rated CurrentNo.(Hex.) Name Description Default Setting(Range)T4-07(3136)Motor Rated CurrentSets the rated current (A) of the motor.Determined by o2-04and C6-01(10% to 200% of thedrive rated current)Note:The value set here becomes the base value for motor protection, the torque limit, and torque control.■T4-08: Motor Rated CapacityNo.(Hex.) Name Description Default Setting(Range)T4-08(3137)Motor RatedCapacity Sets the motor rated capacity in 0.01 kW units.Determined by E9-10(0.10 - 650.00 kW)■T4-09: Number of Motor PolesNo.(Hex.) Name Description Default Setting(Range)T4-09(3138)Number of MotorPoles Sets the number of motor poles.Determined by E9-01(2 - 48)■T4-10: Motor Rated SlipNo.(Hex.) Name Description Default Setting(Range)T4-10(3139)Motor Rated SlipSets the amount of motor rated slip in Hz units.Determined by o2-04(0.000 - 20.000 Hz)Note:The value set here becomes the base value for slip compensation.V/f CL-V/f OLV CLV AOLV OLV/PMOLV/PM AOLV/PM CLV/PM EZOLVV/f CL-V/f OLV CLV AOLV OLV/PMOLV/PM AOLV/PM CLV/PM EZOLVV/f CL-V/f OLV CLV AOLV OLV/PMOLV/PM AOLV/PM CLV/PM EZOLVV/f CL-V/f OLV CLV AOLV OLV/PMOLV/PM AOLV/PM CLV/PM EZOLVV/f CL-V/f OLV CLV AOLV OLV/PMOLV/PM AOLV/PM CLV/PM EZOLVV/f CL-V/f OLV CLV AOLV OLV/PMOLV/PM AOLV/PM CLV/PM EZOLV