Parameter Details1111.8 H: Terminal FunctionsYASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual 769ON : ReverseOFF : ForwardNote:• The motor will not rotate by only turning this signal ON and OFF. Input the Run command.• FWD/REV Command (2-Wire Seq 2) cannot be used at the same time as Forward/Reverse Run Command (2-Wire Seq) [H1-xx = 40,41].■ 44: Offset frequency 1Setting Function Description44 Offset frequency 1Adds the offset frequency set in d7-01 to the frequency reference. when the terminal is turned ON.Note:Refer to “d7: Offset Frequency” for details.■ 45: Offset frequency 2Setting Function Description45 Offset frequency 2Adds the offset frequency set in d7-02 to the frequency reference. when the terminal is turned ON.Note:Refer to “d7: Offset Frequency” for details.■ 46: Offset frequency 3Setting Function Description46 Offset frequency 3Adds the offset frequency set in d7-03 to the frequency reference. when the terminal is turned ON.Note:Refer to “d7: Offset Frequency” for details.■ 47: Node SetupSetting Function Description47 Node SetupWhen the CANopen communication option is utilized, the Node Setup function (a function forsetting the drive node address from the host controller) is enabled.■ 60: DC Injection Braking commandSetting Function Description60 DC Injection Brakingcommand If the DC Injection Braking command is input when the drive is performing stopping operation, DCInjection Braking is applied to stop the motor.DC Injection Braking cancels if the Run command or JOG command are input.The following time chart shows the DC Injection Braking function.Figure 11.81 DC Injection Braking Time ChartV/f CL-V/f OLV CLV AOLV OLV/PMOLV/PM AOLV/PM CLV/PM EZOLVV/f CL-V/f OLV CLV AOLV OLV/PMOLV/PM AOLV/PM CLV/PM EZOLVV/f CL-V/f OLV CLV AOLV OLV/PMOLV/PM AOLV/PM CLV/PM EZOLVV/f CL-V/f OLV CLV AOLV OLV/PMOLV/PM AOLV/PM CLV/PM EZOLVV/f CL-V/f OLV CLV AOLV OLV/PMOLV/PM AOLV/PM CLV/PM EZOLV