Parameter Details1111.9 L: Protection FunctionYASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual 853■ L3-40: CurlimMaxScurveSel duringAcc/DecNo.(Hex.) Name Description Default Setting(Range)L3-40(11D4)CurlimMaxScurveSelduringAcc/Dec Selects whether to enable or disable the optimal S-curve characteristic usedfor current -limited acceleration.0(0, 1)Optimally adjusts and operates the motor acceleration rate used for startup. Enabling this parameter stabilizesacceleration but may cause the acceleration time to be longer than the set time. Set this parameter when faultssuch as oC [Overcurrent] occur immediately after acceleration starts.0 : Disabled1 : EnabledNote:This function is enabled when L3-01 = 3 [Stall Prevent Limit during Accel = ILim Mode].◆ L4: Speed DetectionL4 parameters set the output of signals such as frequency agree and speed detection to the MFDO terminals. Themotor speed is detected when using CLV or CLV/PM.■ L4-01: Speed Agree Detection LevelNo.(Hex.) Name Description Default(Range)L4-01(0499)Speed AgreeDetection Level Sets the speed agree detection level or the motor speed detection level.Determined by A1-02(Determined by A1-02)Sets the speed detection level or motor speed detection level when H2-01 to H2-04 = 2, 3, 4, 5 [MFDO FunctionSelect = Speed Agree 1, User-set Speed Agree 1, Frequency Detection 1, Frequency Detection 2].■ L4-02: Speed Agree Detection WidthNo.(Hex.) Name Description Default(Range)L4-02(049A)Speed AgreeDetection Width Sets the speed agree detection width or motor speed detection width.Determined by A1-02(Determined by A1-02)Sets the speed detection width or motor speed detection width when H2-01 to H2-04 = 2, 3, 4, 5 [MFDOFunction Select = Speed Agree 1, User-set Speed Agree 1, Frequency Detection 1, Frequency Detection 2].■ L4-03: Speed Agree Detect Level (+/-)No.(Hex.) Name Description Default(Range)L4-03(049B)Speed Agree DetectLevel (+/-) Sets the speed agree detection level or the motor speed detection level.Determined by A1-02(Determined by A1-02)Sets the speed detection level or motor speed detection level when H2-01 to H2-04 = 13, 14, 15, 16 [MFDOFunction Select = Speed Agree 2, User-set Speed Agree 2, Frequency Detection 3, Frequency Detection 4].■ L4-04: Speed Agree Detect Width (+/-)No.(Hex.) Name Description Default(Range)L4-04(049C)Speed Agree DetectWidth (+/-) Sets the speed agree detection width or motor speed detection width.Determined by A1-02(Determined by A1-02)V/f CL-V/f OLV CLV AOLV OLV/PMOLV/PM AOLV/PM CLV/PM EZOLVV/f CL-V/f OLV CLV AOLV OLV/PMOLV/PM AOLV/PM CLV/PM EZOLVV/f CL-V/f OLV CLV AOLV OLV/PMOLV/PM AOLV/PM CLV/PM EZOLVV/f CL-V/f OLV CLV AOLV OLV/PMOLV/PM AOLV/PM CLV/PM EZOLVV/f CL-V/f OLV CLV AOLV OLV/PMOLV/PM AOLV/PM CLV/PM EZOLV