Parameter Details1111.3 b: ApplicationYASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual 635For a conveyor, the Dwell function also allows the drive to interlock the output frequency and a delay time for theholding brake on the load side.The Dwell function prevents a PM motor from stepping out by briefly pausing during acceleration. The followingdiagram shows how the Dwell function works.Note:Set b1-03 = 0 [Stopping Method Selection = Ramp to Stop] when using the Dwell function at stop.Figure 11.40 Time Chart for the Dwell Function at Start/Stop■ b6-01: Dwell Reference at StartNo.(Hex.) Name Description Default(Range)b6-01(01B6)Dwell Reference atStart Sets the output frequency to briefly maintain when starting the motor.0.0(Determined by A1-02)Once the drive accelerates to the output frequency set in b6-01, it holds that frequency for the time set in b6-02[Dwell Time at Start], and then resumes acceleration.■ b6-02: Dwell Time at StartNo.(Hex.) Name Description Default(Range)b6-02(01B7)Dwell Time at StartSets the time for the drive to hold the output frequency when starting themotor.0.0 s(0.0 - 10.0 s)■ b6-03: Dwell Reference at StopNo.(Hex.) Name Description Default(Range)b6-03(01B8)Dwell Reference atStop Sets the output frequency to briefly maintain when ramping to stop.0.0(Determined by A1-02)Once the drive decelerates to the output frequency set in b6-03, it holds that frequency for the time set in b6-04[Dwell Time at Stop] and then resumes deceleration.■ b6-04: Dwell Time atNo.(Hex.) Name Description Default(Range)b6-04(01B9)Dwell Time at StopSets the time for the drive to hold the output frequency when ramping tostop.0.0 s(0.0 - 10.0 s)◆ b7: Droop ControlDroop control automatically balances the load level between two motors driving the same load.Droop control reduces motor speed in accordance with changes to the load. The Droop control function needs tobe enabled for each motor it is driving.V/f CL-V/f OLV CLV AOLV OLV/PMOLV/PM AOLV/PM CLV/PM EZOLVV/f CL-V/f OLV CLV AOLV OLV/PMOLV/PM AOLV/PM CLV/PM EZOLVV/f CL-V/f OLV CLV AOLV OLV/PMOLV/PM AOLV/PM CLV/PM EZOLVV/f CL-V/f OLV CLV AOLV OLV/PMOLV/PM AOLV/PM CLV/PM EZOLV