9.4 Model Specifications (400 V Class)368 YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical ManualModelDutyRating4002 4004 4005 4007 4009 4012 4018 4023 4031 4038 4044 4060 4075 4089 4103PowersupplyRatedVoltage/RatedFrequency• Three-phase AC power supply 380 V to 480 V at 50/60 Hz• DC power supply 513 V to 679 VAllowableVoltageFluctuation-15% to +10%AllowableFrequencyFluctuation±5%PowerFacilityCapacity(kVA)HD 1.5 2.8 3.7 5.3 7.1 9.3 13 17 24 33PreparingND 2.0 3.7 5.3 7.1 9.3 13 17 24 33 40*1 The maximum applicable motor output is compliant with 380 V motor ratings as described in Annex G of IEC 60947-4-1. The ratedoutput current of the drive output amps should be equal to or greater than the motor rated current.*2 Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor,wiring connections, and power supply impedance.*3 The rated output capacity is calculated with a rated output voltage of 380 V.Table 9.4 Rating (400 V Class)Model DutyRating 4140 4168 4208 4250 4296 4371 4389Max. Applicable MotorOutput *1(kW)HDPreparingNDInputRated InputCurrent *2(A)HDNDOutputRatedOutputCapacity *3(kVA)HDNDRatedOutputCurrent (A)HDNDOverload Tolerance• Heavy Duty (Rating): 150% of the rated output current for 60 seconds• Normal Duty (Rating): 110% of the rated output current for 60 secondsNote:Derating may be required for applications that start and stop frequently.Carrier FrequencyHD: Usable up to 5 kHz without deratingND: Usable up to 2 kHz without deratingDerating the output current enables use up to a maximum of 10 kHz.Maximum Output Voltage(V)Three-phase 380 V to 480 VNote:The maximum output voltage is proportional to the input voltage.Maximum OutputFrequency• AOLV (Advanced Open Loop Vector Control) and EZOLV (EZ Open Loop Vector Control):120 Hz• CL-V/f (Closed Loop V/f Control), CLV (Closed Loop Vector Control), AOLV/PM(Advanced Open Loop Vector Control for PM), and CLV/PM (Closed Loop Vector Control):400 Hz• V/f (V/f Control), OLV (Open Loop Vector Control), and OLV/PM (Open Loop VectorControl for PM): 590 HzMeasuresforHarmonicsDC reactor Standard internal featuresBrakingDevice Braking Transistor Standard internal features External options