11.6 E: Motor Parameters710 YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manualsettings. Parameter E9-09 is configured with the result of this automatic calculation when “Motor Rated Slip” isset to 0.Note:Parameter E9-09 appears when E9-01 = 0 [Motor Type Selection = IM].■ E9-10: Motor Line-to-Line ResistanceNo.(Hex.) Name Description Default Setting(Range)E9-10(11ED)Motor Line-to-LineResistance Sets the line-to-line resistance for motor stator windings.Determined by o2-04(0.000 - 65.000 Ω)Note:This value represents the motor line-to-line resistance. Be careful not to set this parameter with the single phase resistance.This parameter is automatically set by performing the Stationary Auto-Tuning for Line-to-Line Resistanceprocess. If the Stationary Auto-Tuning for Line-to-Line Resistance process cannot be performed, obtain a testreport from the motor manufacturer. Use the information found on the motor nameplate with any of the followingformulas to calculate the motor line-to-line resistance.• E-type insulation: Multiply 0.92 times the resistance value (Ω) listed on the test report at 75 °C.• B-type insulation: Multiply 0.92 times the resistance value (Ω) listed on the test report at 75 °C.• F-type insulation: Multiply 0.87 times the resistance value (Ω) listed on the test report at 115 °C.V/f CL-V/f OLV CLV AOLV OLV/PMOLV/PM AOLV/PM CLV/PM EZOLV