11.2 A: Initialization Parameters580 YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical ManualUser Parameters No. Parameter No. Saved NameA2-12 H2-01 Terminal M1-M2 Function SelectA2-13 L1-01 Motor Overload Protection SelectA2-14 L4-01 Speed Agree Detection LevelA2-15 L6-02 Torque Detection Level 1A2-16 L6-03 Torque Detection Time 17 : Crane (Traveling)Automatically sets the following parameters for traveling.Table 11.13 Optimal Settings for Traveling ApplicationsNo. Name Optimal ValueA1-02 Control method 0: V/f Controlb1-01 Frequency Reference Selection 1 0: KeypadC1-01 Acceleration Time 1 3.0 sC1-02 Deceleration Time 1 3.0 sC6-01 Normal / Heavy Duty Selection 0: Heavy Duty RatingC6-02 Carrier Frequency Selection 2: 5.0 kHz (4.0 kHz for AOLV/PM)d1-01 Reference 1 6.00 Hzd1-02 Reference 2 30.00 Hzd1-03 Reference 3 60.00 HzH1-05 Terminal S5 Function Select 3: Multi-Step Speed Reference 1H1-06 Terminal S6 Function Select 4: Multi-Step Speed Reference 2H2-01 Terminal M1-M2 Function Select 37: During Frequency OutputH2-02 Terminal M3-M4 Function Select 37: During Frequency OutputH3-06 Terminal A3 Function Selection 1F: Through ModeL3-04 Decel Stall Prevention Selection 0: DisabledL8-05 Input Phase Loss Protect Select 1: EnabledL8-07 Output Phase Loss Protect Select 1: 1PH Loss DetL8-38 Carrier Frequency Reduction 1: Enabled below 6 HzL8-41 High Current Alarm Selection 1: EnabledThe drive saves the following parameters as User Parameters.Table 11.14 Parameters Saved as User Parameters with the Traveling PresetUser Parameters No. Parameter No. Saved NameA2-01 b1-01 Frequency Reference Selection 1A2-02 C1-01 Acceleration Time 1A2-03 C1-02 Deceleration Time 1A2-04 C6-02 Carrier Frequency SelectionA2-05 d1-01 Reference 1A2-06 d1-02 Reference 2A2-07 d1-03 Reference 3A2-08 E2-01 Motor Rated CurrentA2-09 H1-05 Terminal S5 Function SelectA2-10 H1-06 Terminal S6 Function SelectA2-11 H2-01 Terminal M1-M2 Function SelectA2-12 L1-01 Motor Overload Protection Select