2.11 Electrical Installation52 YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manualsignal is output during Restart Enabled and the power supply will turn OFF. Use the interrupt sequence withcaution. The default setting for L5-02 is 0 [Fault output not active].*2 Terminals -, +1, +2, B1 and B2 are the optional connection terminals.NOTICE: Do not connect an AC power supply to terminals -, +1, +2, B1, and B2. Failure to follow the instructions maydamage the drive and the peripheral devices.*3 Be sure to remove the short bar between the terminals +1 and +2 when installing the optional DC reactor.*4 Models 2110 to 2415 and 4060 to 4675 have a built-in DC reactor.*5 Be sure to set L8-55 = 0 [nternalBrakingTransistorProtect = Disabled] when using the regenerativeconverter, regenerative unit or the braking unit (when not using the built-in dynamic braking transistor). rF[Braking Resistor Fault] may be triggered.*6 Set L3-04 = 0 [Decel Stall Prevention Selection = Disabled] to disable Stall Prevention when using aregenerative converter, regenerative unit, dynamic braking unit, braking resistor, or braking resistor unit. Ifleft unchanged, it may not stop at the set deceleration time.*7 When using a braking resistor (ERF type), set L8-01 = 1 [Internal DB Resistor Protect Sel (ERF type)] andbe sure to use a sequence that shuts the power OFF by using the fault relay output for the drive.*8 Wiring for the cooling fan motor is not required with the self-cooling motor.*9 Supplying power to the control circuit separately from the main circuit requires a 24 V power supply beinput to terminal PS-AC.*10 Encoder circuit wiring (wiring on the PG-B3 option card) is not required when using the drive in anapplication that does not use feedback from the motor.*11 Install a jumper between terminals SC-SP-SN to select the type of the power supply of MFDI.NOTICE: Do not short terminals SP and SN. Failure to comply will damage the drive.• Sinking mode: Short terminals SC and SP.• Sourcing mode: Short terminals SC and SN.• External power supply: No jumper necessary.*12 The maximum output current capacity of the +V and -V terminals on the control circuit terminal is 20 mA.NOTICE: Do not install a jumper between terminals +V, -V, and AC. Failure to comply may cause erroneous operation ordamage the drive.*13 Set DIP switches S1-1 to S1-3 to select between a voltage or current input command to terminals A1 to A3.The default setting for S1-1 and S1-3 is voltage reference input (“V” side). The default setting for S1-2 iscurrent reference input (“I” side).*14 Set DIP switch S4 to select between an analog input or PTC input to terminal to A3. After the PTC input hasbeen selected, set DIP switches S1-3 to the V side, and set H3-05= 0 [0-10V (LowLim=0)].*15 Do not connect terminals PS and AC inversely. Failure to comply will damage the drive.*16 Enable the termination resistor in the last drive in a MEMOBUS/Modbus communications by setting DIPswitch S2 to the ON position.*17 Use sourcing mode for Safe Disable input.*18 Disconnect the wire jumper between H1 - HC and H2 - HC when utilizing the Safe Disable input.*19 Monitor outputs work with devices such as analog frequency meters, ammeters, voltmeters, and wattmeters.They are not intended for use as a feedback-type of signal.