Parameter List1010.12 n: Special AdjustmentYASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual 47710.12 n: Special Adjustment◆ n1: Hunting PreventionNo.(Hex.) Name Description Default(Range) Ref.n1-01(0580)Hunting PreventionSelection Enables or disables the hunting prevention function.0 : Disabled1 : Enabled2 : Enable (High carry)1(0 - 2)874n1-02(0581)Hunting PreventionGain Setting Adjusts the behavior of the hunting prevention function. Normallythere is no need to configure this setting.1.00(0.00 - 2.50)874n1-03(0582)Hunting PreventionTime Constant Adjusts the responsiveness (primary delay time constant) of thehunting prevention function. Normally there is no need to configurethis setting.Determined by o2-04(0 - 500 ms)874n1-05(0530)HuntingPreventionGain whileinRev Adjusts the behavior of the hunting prevention function. Used toadjust Reverse run. Normally there is no need to configure thissetting.0.00(0.00 - 2.50)874n1-08(1105)Leak cur antivibSelects the method of suppressing motor vibration caused byleakage current. Normally there is no need to configure this setting.0 : Method11 : Method20(0, 1)875n1-13(1B59)DC BusStabilizationControl Enables or disables the oscillation suppression function for the DCbus voltage.0 : Disabled1 : Enabled0(0, 1)875n1-14(1B5A)DC BusStabilization Time With a setting of n1-13 = 1 [DC Bus Stabilization Control =Enabled], adjustments that address a lack of oscillation suppressioncapability with respect to the DC bus voltage can be made.100.0 ms(50.0 - 500.0 ms)875n1-15(0BF8)Voltage CalibrationSelect Selects the calibration method to be used for the suppression oftorque/current ripple.0 : Calibration Invalid1 : Calibrate only 1 time2 : Calibrate every time1(0 - 2)875n1-16(0BFB)High carry HuntPrev Gain Adjusts the behavior of the hunting prevention function. This ismost effective when a high carrier frequency has been set. Normallythere is no need to configure this setting.0.50(0.00 - 2.50)876n1-17(0BFC)Hunt Prev TimeAdjusts the responsiveness of the hunting prevention function.Normally there is no need to configure this setting.500 ms(0 - 1000 ms)876V/f CL-V/f OLV CLV AOLV OLV/PMOLV/PM AOLV/PM CLV/PM EZOLVV/f CL-V/f OLV CLV AOLV OLV/PMOLV/PM AOLV/PM CLV/PM EZOLVV/f CL-V/f OLV CLV AOLV OLV/PMOLV/PM AOLV/PM CLV/PM EZOLVV/f CL-V/f OLV CLV AOLV OLV/PMOLV/PM AOLV/PM CLV/PM EZOLVV/f CL-V/f OLV CLV AOLV OLV/PMOLV/PM AOLV/PM CLV/PM EZOLVV/f CL-V/f OLV CLV AOLV OLV/PMOLV/PM AOLV/PM CLV/PM EZOLVV/f CL-V/f OLV CLV AOLV OLV/PMOLV/PM AOLV/PM CLV/PM EZOLVV/f CL-V/f OLV CLV AOLV OLV/PMOLV/PM AOLV/PM CLV/PM EZOLVV/f CL-V/f OLV CLV AOLV OLV/PMOLV/PM AOLV/PM CLV/PM EZOLVV/f CL-V/f OLV CLV AOLV OLV/PMOLV/PM AOLV/PM CLV/PM EZOLV