11.3 b: Application628 YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual0 : DisabledThe drive does not use the value set in b5-19 as the PID setpoint.1 : EnabledThe drive uses the value set in b5-19 as the PID setpoint.■ b5-19: PID Setpoint ValueNo.(Hex.) Name Description Default(Range)b5-19(01DD)RUNPID Setpoint ValueThis setting is the PID setpoint when b5-18 = 1 [PID Setpoint Selection =Enabled].0.00%(0.00 - 100.00%)■ b5-20: PID Setpoint ScalingNo.(Hex.) Name Description Default(Range)b5-20(01E2)PID Setpoint ScalingDetermines the units used to set and display b5-19 [PID Setpoint Value].1(0 - 3)0 : 0.01 Hz unitsThe drive uses 0.01 Hz units.1 : 0.01% unitsThe drive uses 0.01% units. Set a value as a percentage of E1-04 [Maximum Output Frequency].2 : min-1The drive uses min -1. Set E2-04, E4-04, or E5-04 [PM Motor Pole Count].3 : User UnitsApplies user-defined units. The drive uses b5-38 [PID Setpoint User Display] and b5-39 [PID Setpoint DisplayDigits].Determines the units to display the PID setpoint in U5-01, U5-04, U5-06 [PID Feedback, PID Setpoint, PIDAdjustedFeedback].■ b5-34: PID Output Lower LimitNo.(Hex.) Name Description Default(Range)b5-34(019F)RUNPID Output LowerLimit Sets the output lower limit for the PID control as a percentage of E1-04[Maximum Output Frequency].0.0%(-100.0 - +100.0%)Use a lower limit to keep PID control output from dropping below a fixed level.Setting b5-34 to 0.0% disables this function.■ b5-35: PID Input LimitNo.(Hex.) Name Description Default(Range)b5-35(01A0)RUNPID Input LimitSets the input upper limit for the PID control as a percentage of E1-04[Maximum Output Frequency].1000.0%(0.0 - 1000.0%)A large input value for PID control creates a high output. This limit is applied to both negative and positivedomains.V/f CL-V/f OLV CLV AOLV OLV/PMOLV/PM AOLV/PM CLV/PM EZOLVV/f CL-V/f OLV CLV AOLV OLV/PMOLV/PM AOLV/PM CLV/PM EZOLVV/f CL-V/f OLV CLV AOLV OLV/PMOLV/PM AOLV/PM CLV/PM EZOLVV/f CL-V/f OLV CLV AOLV OLV/PMOLV/PM AOLV/PM CLV/PM EZOLV