7.2.3 FB 47 - DSTRIKE - Electric door openerWith this block an electric door opener can be controlled, if its not locked with DoorI-sLocked.n With an edge change 0-1 at the input Open for the duration ‘TimeOpening’ ‘Output’ iscontrolled.n With an edge change 0-1 at the input EnableAlwaysOpen respectively DisableAlway-sOpen Open is static activated respectively deactivated. Additionally with set Enable-AlwaysOpen the static output AlwaysOpen is set.n You can connect your door contacts at DoorIsClosed and DoorIsLocked. DoorI-sClosed is set, as soon as the door is closed. DoorIsLocked is set as soon as thedoor is locked, i.e. the contact is controlled by the locking mechanism of the door andopening of the door by means of the electric door opener is disabled.ParametersParameter Declaration Data type DescriptionOpen INPUT BOOL With an edge change 0-1 Output is activated forthe duration of TimeOpening.Default: FALSEEnableAlwaysOpen INPUT BOOL With an edge change 0-1 Output is static set.Default: FALSEDisableAlwaysOpen INPUT BOOL With an edge change 0-1 Output is static reset.Default: FALSETimeOpening INPUT TIME Time for the duration of the activation of Output.Default: 3sDoorIsClosed INPUT BOOL n Optional - Position doorTRUE: Door is closedFALSE: Door is openDefault: FALSEDoorIsLocked INPUT BOOL n Optional - Lock state of the door– TRUE: Door is locked– FALSE: Door is not lockedDefault: FALSEOutput OUTPUT BOOL Static output to drive a monostable relay.AlwaysOpen OUTPUT BOOL Static output to indicate "Door is static open".DescriptionVIPA SPEED7Building ControlRoom > FB 47 - DSTRIKE - Electric door openerHB00 | OPL_SP7 | Operation list | en | 18-30106