Group IDs of the measurands Group IDs of the measurands Group IDs of the measurands1 1, 2, 3 6 16, 17, 18 11 31, 32, 332 4, 5, 6 7 19, 20, 21 12 34, 35, 363 7, 8, 9 8 22, 23, 24 13 37, 38, 394 10, 11, 12 9 25, 26, 27 14 40, 415 13, 14, 15 10 28, 29, 30The measured values read are entered in the corresponding variables of Data.[Name ofthe measurand].Value. For unread measured values Value = 0.You can trigger commands via the data structure MEAS_DATA by setting the corre-sponding bits in the variable Header.Cmd. If several bits are set, they are sequentiallyprocessed. Here, the following commands are available:n Bit 0: Reset all the energy countersn Bit 1: Trigger reset on the current transformern Bit 2: Reset status measurementn Bit 3: Writing the energy setpoints from "SetValues" to the ID3 ... ID8.n Error messages that occur during the initialization of the block or when reading meas-ured values can be found in the data structure MEAS_DATA atHeader.Status_Global.n Error messages that occur during command processing can be found atHeader.Status_Cmd and the detailed information at Header.Error_IDn In the event of an error, the function block continues the order processing. Here, thefaulty jobs are repeated. The measured values in the data structure MEAS_DATA arenot affected by error messages.12.2.2 FB 325 - EM_COM_R1 - Communication with 031-1PAxxThis block enables the communication with the modules 031-1PAxx for energy meteringand power measurement. For the communication a data block is necessary. Here the DBgets its structure from the UDT 325 EM_DATA_R1. The block has the following function-alities:n Load default parameters after start-upn Storage of parameters, limit values, measured values and messagesn Transfer of consistent measured valuesn Writing set pointsn Definition of the measured values by means of an UDT structuren Communication by means of telegram type and IDn Functional diagnostics, connection monitoring and error message evaluationCommand InterfaceError behaviorOverviewVIPA SPEED7 Device SpecificEnergy Measurement > FB 325 - EM_COM_R1 - Communication with 031-1PAxxHB00 | OPL_SP7 | Operation list | en | 18-30 267