For events of the class A and B, yz refers to the message number that was predefined inhexadecimal representation when the messages were configured.INFO1 contains information with a length of one word. The following data types are valid:n WORDn INTn ARRAY [0...1] OF CHARINFO1 can be integrated as associated value into the message text, i.e. to add currentinformation to the message.INFO2 contains information with a length of two words. The following data types are valid:n DWORDn DINTn REALn TIMEn ARRAY [0...3] OF CHARINFO2 can be integrated as associated value into the message text, i.e. to add currentinformation to the message.The return value contains an error code if an error is detected when the function is beingprocessed.Value Description0000h no error0091h No partner registered (the diagnostic event has been entered into the diagnostic buffer)8083h Data type INFO1 not valid8084h Data type INFO2 not valid8085h EVENTN not valid8086h Length of INFO1 not valid8087h Length of INFO2 not valid8091h Error message identical to error code 0091h8092h Send operation currently not possible, send buffer full(the diagnostic event has been entered into the diagnostic buffer)14.1.41 FC/SFC 53 - uS_Tick - Time measurementThis block allows you to read the μs ticker integrated in the SPEED7-CPU. The μs tickeris a 32bit μs time counter that starts at every reboot with 0 and counts to 232-1μs. At over-flow the counter starts again with 0. With the help of the difference creation of theRETVAL results of 2 FC/SFC 53 calls before and after an application you may thus eval-uate the runtime of the application in μs.INFO1INFO2RET_VAL (Return value)VIPA SPEED7 Integrated StandardSystem Functions > FC/SFC 53 - uS_Tick - Time measurementHB00 | OPL_SP7 | Operation list | en | 18-30 689