The following codes can be returned:Code Description0x0000 No error0x80D0 Channel 0 not in status active0x80D1 Channel 1 not in status active0x80D6 Channel 0: Input value RESOLUTION_CH0 = 00x80D7 Channel 1: Input value RESOLUTION_CH1 = 00x80D8 Channel 0: Input value RESOLUTION_CH0 < 00x80D9 Channel 1: Input value RESOLUTION_CH1 < 00x80DA Channel 0: Measured time value = 00x80DB Channel 1: Measured time value = 00x80DC Channel 0: Measured time value < 00x80DD Channel 1: Measured time value < 00x80DE Channel 0: Measured time value > 0x7FFFFFF0x80DF Channel 1: Measured time value > 0x7FFFFFF0x80E2 Channel 0: Determined number of edges < 00x80E3 Channel 1: Determined number of edges < 00x80E4 Channel 0: Determined number of edges > 0xFFFFFF0x80E5 Channel 1: Determined number of edges > 0xFFFFFF0x80E6 Channel 0: Determined rotational speed > max. (DINT)0x80E7 Channel 1: Determined rotational speed > max. (DINT)0x80E8 Channel 0: No valid measurement within the entered measurement period0x80E9 Channel 1: No valid measurement within the entered measurement period12.2 Energy Measurement12.2.1 Overview12.2.1.1 TermsA measurand is a physical quantity that can be measured such as current, voltage ortemperature.A measured value is a value of a measurand, which is determined by measurement or bycalculation.In the module each measurand one ID is assigned. The access to the measured value ofa measurand happens by means of the corresponding ID.ERROR (Return value)MeasurandMeasured valueIDVIPA SPEED7Device SpecificEnergy Measurement > OverviewHB00 | OPL_SP7 | Operation list | en | 18-30264