DONE(SEND)NDR(RECV)ERROR STATUS Description0 0 1 8091h Module start address not within double word grid.0 0 1 8092h ANY reference contains type setting unequal BYTE.- 0 1 80A0h Negative acknowledgement at reading from module.0 0 1 80A4h reserved0 0 1 80B0h Module doesn’t recognize the record set.0 0 1 80B1h The length setting (in parameter LEN) is invalid.0 0 1 80B2h reserved0 0 1 80C0h Record set not readable.0 0 1 80C1h The set record set is still in process.0 0 1 80C2h There is a job jam.0 0 1 80C3h The operating sources (memory) of the CPU are temporarilyoccupied.0 0 1 80C4h Communication error (occurs temporarily; a repetition in theuser application is reasonable).0 0 1 80D2h Module start address is wrong.At a reboot of the CP, the output parameters are set as follows:n DONE = 0n NDR = 0n ERROR = 0n STATUS = 8180h (at AG_RECV)n STATUS = 8181h (at AG_SEND)8.2.4 FC 10 - AG_CNTRL - Control CP 343The connections of the Ethernet CP 343 may be diagnosed and initialized by means ofthe VIPA FC 10.The following jobs may be executed by parameterizable commands:n Reading connection informationn Resetting configured connectionsThe commands of this block are permitted only for SEND/RECV connections based onthe ISO/RFC/TCP and UDP protocols.Please note that this block calls the FC or SFC 196 AG_CNTRL inter-nally. These must not be overwritten! The direct call of an internal blockleads to errors in the corresponding instance DB!The following diagram shows a typical sequence of AG_CNTRL. Here it is shown how theconnection status is initially queried and then, in a second job, how the connection termi-nation is triggered with the rest command.Status parameter at rebootDescriptionFC 10 in the user programVIPA SPEED7Network CommunicationEthernet Communication > FC 10 - AG_CNTRL - Control CP 343HB00 | OPL_SP7 | Operation list | en | 18-30144