OB83_EV_CLASS OB83_FLT_ID Description39h 51h PROFINET IO module removed54h PROFINET IO submodule removed38h 54h PROFINET IO submodule inserted and matches configured submodule55h PROFINET IO submodule inserted, but does not match configured sub-module56h PROFINET IO submodule inserted, but error with module parameters58h PROFINET IO submodule, access error corrected39h 61h Module removed or not responding OB83_MDL_TYPE: Actual moduletype38h 61h Module inserted. Module type OK OB83_MDL_TYPE: Actual moduletype63h Module inserted but incorrect module type OB83_MDL_TYPE: Actualmodule type64h Module inserted but problem (module ID cannot be read)OB83_MDL_TYPE: Configured module type65h Module inserted but error in module parameter assignmentOB83_MDL_TYPE: Actual module type39h 66h Module not responding, load voltage error38h 66h Module responds again, load voltage error corrected33h 67h Start of module reconfiguration32h 67h End of module reconfiguration39h 68h Module reconfiguration terminated with errorIf you are using a DP-V1- or PROFINET-capable CPU you can obtainadditional information on the interrupt with the help of SFB 54 "RALRM"which exceeds the start information of the OB.6.9.5 OB 85 - OBNL_FLT - Priority Class ErrorThe operating system of the CPU calls OB 85 whenever one of the following eventsoccurs:n Start event for an OB that has not been loadedn Error when the operating system accesses a blockn I/O access error during update of the process image by the system (if the OB 85 callwas not suppressed due to the configuration)The OB 85 may be delayed by means of the SFC 41 and re-enabled by the SFC 42.If OB 85 has not been programmed, the CPU changes to STOP modewhen one of these events is detected.DescriptionVIPA SPEED7Organization BlocksAsynchronous error Interrupts > OB 85 - OBNL_FLT - Priority Class ErrorHB00 | OPL_SP7 | Operation list | en | 18-3092