Parameter Declaration Data type Memory area DescriptionG INPUT BOOL I, Q, M, D, LConstantSelection switchIN0 INPUT ANY I, Q, M, D, L 1. Input valueIN1 INPUT ANY I, Q, M, D, L 2. Input valueRET_VAL OUTPUT ANY I, Q, M, D, L Selected input value15.2.38 FC 37 - STRNG_DI - Convert STRING to DINTThe function FC 37 converts a string to a variable in DINT data format.n The first character in the string may be a sign or a number, the characters which thenfollow must be numbers.n If the length of the string is equal to zero or greater than 11, or if invalid characters arefound in the string, no conversion takes place and the BR bit is set to "0".n If the result of the conversion is outside the DINT range, the result is limited to thecorresponding value and the BR bit is set to "0".Parameter Declaration Data type Memory area DescriptionS* INPUT STRING D, L Input stringRET_VAL OUTPUT DINT I, Q, M, D, L Result*) You can assign only a symbolically defined variable for the parameter.15.2.39 FC 38 - STRNG_I - Convert STRING to INTThe function FC 38 converts a string to a variable in INT data format.n The first character in the string may be a sign or a number, the characters which thenfollow must be numbers.n If the length of the string is equal to zero or greater than 6, or if invalid characters arefound in the string, no conversion takes place and the BR bit is set to "0".n If the result of the conversion is outside the INT range, the result is limited to the cor-responding value and the BR bit is set to "0".Parameter Declaration Data type Memory area DescriptionS* INPUT STRING D, L Input stringRET_VAL OUTPUT INT I, Q, M, D, L Result*) You can assign only a symbolically defined variable for the parameter.ParameterDescriptionParameterDescriptionParameterVIPA SPEED7StandardIEC > FC 38 - STRNG_I - Convert STRING to INTHB00 | OPL_SP7 | Operation list | en | 18-30820