POS_P_ON NEG_P_ON QPOS_P QNEG_PThree-step con-trolFALSE FALSE FALSE FALSETRUE FALSE TRUE FALSEFALSE TRUE FALSE TRUETRUE TRUE FALSE FALSETwo-step con-trolFALSE Any FALSE TRUETRUE Any TRUE FALSEComplete Restart/Restartn During a complete restart, all the signal outputs are set to 0.The block does not check for errors, so no error Information is output.15.5.4 FB 58 - TCONT_CP - Continuous Temperature ControlFB 58 TCONT_CP is used to control temperature processes with continuous or pulsedcontrol signals. You can set parameters to enable or disable subfunctions of the PID con-troller and adapt it to the process.ParametersParameter Declaration Data Type DescriptionPV_IN INPUT REAL PROCESS VARIABLE INn An initialization value can be set at the PV_IN inputor an external process variable in floating-pointformat can be connected.n Default: 0.0n Dependent on the sensors usedPV_PER INPUT WORD PROCESS VARIABLE PERIPHERYn The process variable in the peripheral I/O format isconnected to the controller at the PV_PER input.n Default: 0DISV INPUT REAL DISTURBANCE VARIABLEn For feed forward control, the disturbance variable isconnected to the DISV input.n Default: 0.0INT_HPOS INPUT BOOL INTEGRAL ACTION HOLD IN POSITIVE DIRECTIONn The output of the integral action can be blocked ina positive direction. To achieve this, the INT_HPOSinput must be set to TRUE. In a cascade control,the INT_HPOS of the primary controller is intercon-nected to QLMN_HLM of the secondary controller.n Default: FALSEModesError InformationDescriptionVIPA SPEED7StandardPID Control > FB 58 - TCONT_CP - Continuous Temperature ControlHB00 | OPL_SP7 | Operation list | en | 18-30854