17.23 Module diagnostic information via logical address - SSL-ID: 00B3hIf you read this partial list, you obtain all the diagnostic data of a module. You can alsoobtain this information for PROFIBUS DP and submodules. The diagnostic record 1 con-tains the 4 bytes of diagnostic data that are also in data record 0, plus module-specificdiagnostics data that describe the state of a channel or a channel group. The module is tobe specified via the logical base address.Content Value DescriptionSSL_ID 00B3h Shows all the diagnostic data of a module.INDEX xxxxh Here the following is to be specified via INDEX:n Bit 0 ... 14: Logical base address of the modulen Bit 15:– 0: Input– 1: OutputLENTHDR xxxxh The length of the record set depends on the module.N_DR 0001h Number of record set (1)Information to length and structure of the diagnostic data may be found inthe corresponding manual of your diagnosable module.DescriptionHeaderRecord setVIPA SPEED7 SSL System status listModule diagnostic information via logical address - SSL-ID: 00B3hHB00 | OPL_SP7 | Operation list | en | 18-30 991