Setting Options MenuPage 45Lock SetUse this setting if you are using a lock to set the system.To use Lock Set, you must: Configure a Lock Set zone (see page 28) that is activated by a suitable lock(located on the final exit door). Configure a Final Exit zone (see page 26) connected to the final exit door.Setting: Once the user has started the setting sequence, the exit tone sounds, whichcontinues until the user closes the Final Exit door and operates the lock. When theSettle Time (page 45) expires, the control unit sets the system and converts the FinalExit zone to a zone of type Normal Alarm.Unsetting: When a user de-activates the Lock Set zone, the control unit convertsany zone originally programmed as Final Exit back to Final Exit (so that the entry timestarts when the user opens the entry door) and starts a warning tone (distinct fromthe entry tone). If the user activates the Lock Set zone again without starting theEntry Timer, the control unit changes all Final Exit zones back into Normal Alarmzones and stops the warning tone.Note: If you use Lock Set, you must set After Entry (page 53) to Never in order todisable confirmation and comply with BS8243.Exit TerminateSetting: The user must start the setting sequence in the normal way, and thencomplete setting in one of the following ways once they have left the protected area:a) By activating an Exit Terminate zone (see page 28).b) By presenting a proximity reader tag to a KEY-EP external proximity readerconnected to a suitable keypad. This requires System Options – User Options – UserAccess – Terminated Set to be set to Y (page 49).When the user starts the setting sequence, the exit tone is sounded and the exit timedoes not expire. Once the user completes the setting sequence, the system setswhen the Settle Time (page 45) expires.The user can unset using any of the following methods:a) By presenting a proximity tag to an external proximity tag reader.c) By activating a Final Exit zone (to start an entry timer) and then entering an accesscode or presenting a proximity tag to a keypad. Note: This method does not complywith BS8243 clause 6.4.Settle TimeThis option is available only if Exit Mode is set to Final Door Set, Lock Set or ExitTerminate. This option allows you to define a time delay to allow detectors to settle beforethe system sets. During this period, the sounders stop and the control unit ignores anyalarms generated by the detectors.Enter two digits to specify a time in seconds, from 01 to 30.Confirm SetThis option is available only if Exit Mode is set to Instant Set. Selecting On causes anaudible confirmation beep at the end of the Exit Time. Selecting Off causes no audibleconfirmation beep at the end of the Exit Time.