System Options MenuPage 55Unconfirm Confirm Unconfirmed alarm: keypads and loudspeakers soundimmediately and run for the Siren Time.Confirmed alarm: the control unit waits for any Siren Delay(see page 46), and then starts the alarm sound at sirens andrestarts the sound at all keypads and loudspeakers. Thisruns for the Siren Time.Confirm Confirm Unconfirmed alarm: No alarm sounds.Confirmed alarm: the control unit waits for any Siren Delay,and then starts the alarm sound at all keypads loudspeakersand sirens. This runs for the Siren Time.Siren OnUnconfirmThe control unit operates the siren for all alarms (and overrides any Siren Delay).ConfirmWhen the system is set, the control unit does not activate the siren(s) until aconfirmed alarm occurs.The behaviour of sounders and sirens is described in Table 6.Unconfirmed ResetThis is available only when Confirmation Mode is set to DD243 or BS8243. The setting forthis option overrides System Options – User Options – User Reset – Zone Alarms (seepage 49).UserThe user can reset after an unconfirmed alarm.InstallerThe user cannot reset after an unconfirmed alarm; the installer must do it.Note: If a user silences an alarm within the Abort Time (page 57), the alarm will notrequire an installer reset. These options apply to intruder alarms only and not to Hold-Up Alarms.Confirmed ResetThis is available only when Confirmation Mode is set to DD243 or BS8243. The setting forthis option overrides System Options – User Options – User Reset – Zone Alarms (seepage 49).UserThe user can reset after a confirmed alarm.InstallerThe user cannot reset after a confirmed alarm; the installer must do it.Note: If a user silences an alarm within the Abort Time (page 57), the alarm will notrequire an installer reset.