3.13 Wiring ChecklistNo. Item Page(s)Drive, Peripherals, Option Cards1 Check drive model number to ensure receipt of correct model. 312 Make sure you have the correct braking resistors, DC link chokes, noise filters, and other peripheral devices. 3763 Check the option card model number. 376Installation Area and Physical Setup4 Ensure that the area surrounding the drive complies with specifications. 48Power Supply Voltage, Output Voltage5 The voltage from the power supply should be within the input voltage specification range of the drive. 1916 The voltage rating for the motor should match the drive output specifications. 312857 Verify that the drive is properly sized to run the motor.Main Circuit Wiring8 Confirm proper branch circuit protection as specified by national and local codes. 689Properly wire the power supply to drive terminals R/L1, S/L2, and T/L3.Note: Confirm the following when wiring models 4A0930 and 4A1200:• Remove the jumpers shorting terminals R/L1-R1/L11, S/L2-S1/L21, and T/L3-T1/L31 whenoperating with 12-pulse rectification. Refer to 12-Pulse Rectification on page 73 for details.• When operating without 12-pulse rectification, properly wire terminals R1/L11, S1/L21, andT1/L31 in addition to terminals R/L1, S/L2, and T/L3.7110 Properly wire the drive and motor together.The motor lines and drive output terminals R/T1, V/T2, and W/T3 should match in order to produce the desired phaseorder. If the phase order is incorrect, the drive will rotate in the opposite direction. 9311 Use 600 Vac vinyl-sheathed wire for the power supply and motor lines. 8512Use the correct wire gauges for the main circuit. Refer to Main Circuit Wire Gauges and Tightening Torques on page85.• Consider the amount of voltage drop when selecting wire gauges. Increase the wire gauge when the voltage drop isgreater than 2% of motor rated voltage. Ensure the wire gauge is suitable for the terminal block. Use the followingformula to calculate the amount of voltage drop:Line drop voltage (V) = 3 × wire resistance (Ω/km) × wire length (m) × current (A) × 10-3• If the cable between the drive and motor exceeds 50 m, adjust the carrier frequency set to C6-02 accordingly.859313 Properly ground the drive. Review page 93. 9314 Tighten control circuit and grounding terminal screws. Refer to Main Circuit Wire Gauges and Tightening Torques onpage 85. 8515Set up overload protection circuits when running multiple motors from a single drive.M1OL1OL2OLnMC1MC2MCnM2MnDriveMC1 - MCnOL 1 - OL n... magnetic contactor... thermal relayPower supplyNote: Close MC1 – MCn before operating the drive. MC1 – MCn cannot be switched off during run.–16 Install a magnetic contactor when using a dynamic braking option. Properly install the resistor and ensure that overloadprotection shuts off the power supply using the magnetic contactor. 38217 Verify phase advancing capacitors, input noise filters, or GFCIs are NOT installed on the output side of the drive. –Control Circuit Wiring18 Use twisted-pair line for all drive control circuit wiring. 9819 Ground the shields of shielded wiring to the GND terminal. 9820 For 3-Wire sequence, set parameters for multi-function contact input terminals S1 – S8, and wire control circuits. –21 Properly wire any option cards. 9822 Check for any other wiring mistakes. Only use a multimeter to check wiring. –23 Properly fasten drive control circuit terminal screws. Refer to Main Circuit Wire Gauges and Tightening Torques onpage 85. 853.13 Wiring ChecklistYASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual 1053 Electrical Installation