n L5-02: Auto Restart Fault Output Operation SelectionDetermines if a fault output is triggered (H2-oo = E) when the drive attempts to restart.No. Name Setting Range DefaultL5-02 Auto Restart Fault Output Operation Selection 0, 1 0Setting 0: No Fault OutputAuto-Restart - Cancel EarlyFault output disabled (L5-02 = 0)Run commandFault conditionFault displayFault digital outputOutput Frequency(U1-02)L5-04Figure 5.81 Auto Restart Cancel EarlySetting 1: Fault Output Is Setn L5-04: Fault Reset Interval TimeDetermines the amount of time to wait between restart attempts when parameter L5-05 is set to 1.No. Name Setting Range DefaultL5-04 Fault Reset Interval Time 0.5 to 600.0 s 10.0 sn L5-05: Fault Reset Operation SelectionNo. Name Setting Range DefaultL5-05 Fault Reset Operation Selection 0, 1 0Setting 0: Count Successful RestartsThe drive will continuously attempt to restart. If it restarts successfully, the restart counter is increased. This operation isrepeated each time a fault occurs until the counter reaches the value set to L5-01.Setting 1: Count Restart AttemptsThe drive will attempt to restart using the time interval set to parameter L5-04. A record is kept of the number of attempts torestart to the drive, regardless of whether those attempts were successful. When the number of attempted restarts exceeds thevalue set to L5-01, the drive stops attempting to restart.u L6: Torque DetectionThe drive provides two independent torque detection functions that trigger an alarm or fault signal when the load is too heavy(oL), or suddenly drops (UL). These functions are set up using the L6-oo parameters. Program the digital outputs as shownbelow to indicate the underload or overload condition to an external device:Note: When overtorque occurs in the application, the drive may stop due to overcurrent (oC) or overload (oL1). To prevent the drive from stopping,use torque detection to indicate an overload situation to the controller before oC or oL1 occur. Use undertorque detection to discoverapplication problems like a torn belt, a pump shutting off, or other similar trouble.5.8 L: Protection FunctionsYASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual 2555 Parameter Details