Drive Model Terminal Recomm. Gaugemm2 (AWG, kcmil)Wire Rangemm2 (AWG, kcmil)ScrewSizeTightening TorqueN·m (lb.in.)5A0145R/L1, S/L2, T/L3 95(3/0)95 to 150(2/0 to 300)M10 18 to 23(159 to 204)U/T1, V/T2, W/T3 95(3/0)95 to 150(2/0 to 300)⊖, ⊕1 – 70 to 95(3/0 to 4/0)⊕3 – 70 to 95(1/0 to 2/0)35(3)35 to 150(3 to 300)5A0192R/L1, S/L2, T/L3 185(300)95 to 300(2/0 to 600)M12 32 to 40(283 to 354)U/T1, V/T2, W/T3 150(250)95 to 300(2/0 to 600)⊖, ⊕1 – 95 to 185(2/0 to 400)⊕3 – 95 to 120(2/0 to 250) M10 18 to 23(159 to 204)50(1)35 to 300(1 to 350) M12 32 to 40(283 to 354)5A0242R/L1, S/L2, T/L3 240(400)95 to 300(2/0 to 600)M12 32 to 40(283 to 354)U/T1, V/T2, W/T3 185(350)95 to 300(2/0 to 600)⊖, ⊕1 – 95 to 240(2/0 to 500)⊕3 – 150(250 to 300) M10 18 to 23(159 to 204)50(1)35 to 300(1 to 350) M12 32 to 40(283 to 354)Closed-Loop Crimp Terminal RecommendationsTo maintain UL/cUL approval, UL Listed closed-loop crimp terminals are specifically required when wiring the drive maincircuit terminals on models 2A0110 to 2A0415, 4A0058 to 4A1200, and 5A0041 to 5A0242. Use only the tools recommendedby the terminal manufacturer for crimping. Yaskawa recommends crimp terminals made by JST and Tokyo DIP (or equivalent)for the insulation cap. Table D.7 matches the wire gauges and terminal screw sizes with Yaskawa-recommended crimpterminals, tools, and insulation caps. Refer to the appropriate Wire Gauge and Torque Specifications table for the wire gaugeand screw size for your drive model. Place orders with a Yaskawa representative or the Yaskawa sales department.Wire gauge values shown in bold italic are the recommended values. Refer to local codes for proper selections.Table D.7 Closed-Loop Crimp Terminal SizeDrive ModelWire Gauge (AWG, kcmil) ScrewSizeCrimpTerminalModelNumberTool InsulationCap ModelNo. Code <1>R/L1, S/L2, T/L3 U/T1, V/T2, W/T3 Machine No. Die Jaw200 V Class2A00042A00062A00082A001014M4R2-4YA-4 AD-900TP-003 100-054-02812 R5.5-4 TP-005 100-054-029102A001214 14M4R2-4YA-4 AD-900TP-003 100-054-02812 12 R5.5-4 TP-005 100-054-029102A0018– 14M4R2-4YA-4 AD-900TP-003 100-054-02812 R5.5-4 TP-005 100-054-029102A0021 12 M4 R5.5-4 YA-4 AD-900 TP-005 100-054-02910D.3 UL and CSA Standards558 YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual