n E2-03: Motor No-Load CurrentSet the no-load current for the motor in amperes when operating at the rated frequency and the no-load voltage. The drive setsE2-03 during the Auto-Tuning process (Rotational Auto-Tuning and Stationary Auto-Tuning 1, 2). The motor no-load currentlisted in the motor test report can also be entered to E2-03 manually. Contact the motor manufacturer to receive a copy of themotor test report.No. Parameter Name Setting Range DefaultE2-03 Motor No-Load Current 0 to [E2-01](unit: 0.01 A) Determined byo2-04Note: The number of decimal places in the parameter value depends on the drive model 1. This value has two decimal places (0.01 A) if the driveis set for a maximum applicable motor capacity up to and including 11 kW, and one decimal place (0.1 A) if the maximum applicable motorcapacity is higher than 11 kW. Refer to Power Ratings on page 394 for details.n E2-04: Number of Motor PolesSet the number of motor poles to E2-04. If Auto-Tuning completes successfully, the value entered to T1-06 will automaticallybe saved to E2-04.No. Parameter Name Setting Range DefaultE2-04 Number of Motor Poles 2 to 48 4n E2-05: Motor Line-to-Line ResistanceSets the line-to-line resistance of the motor stator winding. If Auto-Tuning completes successfully, this value is automaticallycalculated. Enter this value as line-to-line and not for each motor phase.If Auto-Tuning is not possible, contact the motor manufacturer to find out the line-to-line resistance or measure it manually.When using the manufacturer motor test report, calculate E2-05 by one of the formulas below:• E-type insulation: Multiply 0.92 times the resistance value (Ω) listed on the test report at 75 °C.• B-type insulation: Multiply 0.92 times the resistance value (Ω) listed on the test report at 75 °C.• F-type insulation: Multiply 0.87 times the resistance value (Ω) listed on the test report at 115 °C.No. Parameter Name Setting Range DefaultE2-05 Motor Line-to-Line Resistance 0.000 to 65.000 mΩ <1> Determined byo2-04<1>n E2-06: Motor Leakage InductanceSets the voltage drop due to motor leakage inductance as a percentage of motor rated voltage. This value is automatically setduring Auto-Tuning (Rotational Auto-Tuning, Stationary Auto-Tuning 1, 2).No. Parameter Name Setting Range DefaultE2-06 Motor Leakage Inductance 0.0 to 40.0% Determined byo2-04n E2-10: Motor Iron Loss for Torque CompensationSets the motor iron loss in watts.No. Parameter Name Setting Range DefaultE2-10 Motor Iron Loss for Torque Compensation 0 to 65535 W Determined byo2-04n E2-11: Motor Rated PowerSets the motor rated power in kW. If Auto-Tuning completes successfully, the value entered to T1-02 will automatically besaved to E2-11.No. Parameter Name Setting Range DefaultE2-11 Motor Rated Power 0.00 to 650.00 kW Determined byo2-045.5 E: Motor Parameters196 YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual