No.(Addr.Hex) Name Description Values Paged4-05(2AC) Frequency Reference BiasOperation Mode Selection(Up/Down 2)0: Bias value is held if no input Up 2 or Down 2 is active.1: When the Up 2 reference and Down 2 reference are both on or both off, theapplied bias becomes 0. The specified accel/decel times are used foracceleration or deceleration.Default: 0Range: 0, 1 188d4-06(2AD) Frequency Reference Bias(Up/Down 2)The Up/Down 2 bias value is saved in d4-06 when the frequency reference isnot input by the digital operator. Set as a percentage of the maximum outputfrequency.Default: 0.0%Min.: -99.9Max.: 100.0 189d4-07(2AE) Analog FrequencyReference Fluctuation Limit(Up/Down 2)Limits how much the frequency reference is allowed to change while an inputterminal set for Up 2 or Down 2 is enabled. If the frequency reference changesfor more than the set value, then the bias value is held and the drive acceleratesor decelerates to the frequency reference. Set as a percentage of the maximumoutput frequency.Default: 0.01%Min.: 0.01Max.: 100.0 189d4-08(2AF) Frequency Reference BiasUpper Limit (Up/Down 2)Sets the upper limit for the bias and the value that can be saved in d4-06. Setas a percentage of the maximum output frequency. Default: 1.0%Min.: 0.0Max.: 100.0 189d4-09(2B0) Frequency Reference BiasLower Limit (Up/Down 2)Sets the lower limit for the bias and the value that can be saved in d4-06. Setas a percentage of the maximum output frequency. Default: 0.0%Min.: -99.9Max.: 0.0 189d4-10(2B6) Up/Down FrequencyReference Limit Selection 0: The lower limit is determined by d2-02 or an analog input.1: The lower limit is determined by d2-02. Default: 0Range: 0, 1 189u d6: Field Weakening and Field ForcingNo.(AddrHex.) Name Description Values Paged6-01(2A0) Field Weakening LevelSets the drive output voltage for the Field Weakening function as a percentageof the maximum output voltage.Enabled when a multi-function input is set for Field Weakening (H1-oo =63).Default: 80%Min.: 0Max.: 100 190d6-02(2A1) Field Weakening FrequencyLimitSets the lower limit of the frequency range where Field Weakening control isvalid.The Field Weakening command is valid only at frequencies above this settingand only when the output frequency matches the frequency reference (speedagree).Default: 0.0 HzMin.: 0.0Max.: 400.0 190B.5 d: ReferencesYASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual 445B Parameter List