Drive Model Terminal Recomm. GaugeAWG, kcmil Wire RangeAWG, kcmil ScrewSize Tightening TorqueN·m (lb.in.)2A0250R/L1, S/L2, T/L3 3/0 × 2P 3/0 to 300M12 32 to 40(283 to 354)U/T1, V/T2, W/T3 3/0 × 2P 3/0 to 300⊖, ⊕1 – 3/0 to 300⊕3 – 2 to 300 M10 18 to 23(159 to 204)3 3 to 300 M12 32 to 40(283 to 354)2A0312R/L1, S/L2, T/L3 4/0 × 2P 3/0 to 300M12 32 to 40(283 to 354)U/T1, V/T2, W/T3 3/0 × 2P 3/0 to 300⊖, ⊕1 – 3/0 to 300⊕3 – 3/0 to 300 M10 18 to 23(159 to 204)2 2 to 300 M12 32 to 40(283 to 354)2A0360R/L1, S/L2, T/L3 250 × 2P 4/0 to 600M12 32 to 40(283 to 354)U/T1, V/T2, W/T3 4/0 × 2P 4/0 to 600⊖, ⊕1 – 250 to 600⊕3 – 3/0 to 600 M10 18 to 23(159 to 204)1 1 to 350 M12 32 to 40(283 to 354)2A0415R/L1, S/L2, T/L3 350 × 2P 250 to 600M12 32 to 40(283 to 354)U/T1, V/T2, W/T3 300 × 2P 300 to 600⊖, ⊕1 – 300 to 600⊕3 – 3/0 to 600 M10 18 to 23(159 to 204)1 1 to 350 M12 32 to 40(283 to 354)<1> Install a GFCI when using this wire gauge in accordance with IEC/EN 61800-5-1.<2> Install a GFCI, or use 10 mm2 (AWG 8) copper wire when using this wire gauge in accordance with IEC/EN 61800-5-1.Note: When connecting peripheral devices or options to terminals ⊖, ⊕1, ⊕3, B1, and B2, refer to the instruction manual for each device. Formore information, contact Yaskawa or your nearest sales representative.n Three-Phase 400 V ClassTable 3.4 Wire Gauge and Torque Specifications (Three-Phase 400 V Class)Drive Model Terminal Recomm. GaugeAWG, kcmil Wire RangeAWG, kcmil ScrewSize Tightening TorqueN·m (lb.in.)4A00024A0004R/L1, S/L2, T/L3 14 14 to 10M4 1.2 to 1.5(10.6 to 13.3)U/T1, V/T2, W/T3 14 14 to 10⊖, ⊕1, ⊕2 – 14 to 10B1, B2 – 14 to 1012 <1> 14 to 124A00054A00074A0009R/L1, S/L2, T/L3 14 14 to 10M4 1.2 to 1.5(10.6 to 13.3)U/T1, V/T2, W/T3 14 14 to 10⊖, ⊕1, ⊕2 – 14 to 10B1, B2 – 14 to 1010 <1> 14 to 104A0011R/L1, S/L2, T/L3 12 14 to 10M4 1.2 to 1.5(10.6 to 13.3)U/T1, V/T2, W/T3 14 14 to 10⊖, ⊕1, ⊕2 – 14 to 10B1, B2 – 14 to 1010 <1> 14 to 103.8 Main Circuit WiringYASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual 873 Electrical Installation