Parameter Name Pageb5-39 PID Setpoint Display Digits 170b5-46 PID Unit Selection 170b5-90 EZ Sleep Unit 171b5-91 EZ Minimum Speed 171b5-92 EZ Sleep Level 171b5-94 EZ Wake-up Level 171C1-01 Acceleration Time 1 177C1-02 Deceleration Time 1 177E2-01 Motor Rated Current 195H3-09 Terminal A2 Signal Level Selection 226L5-01 Number of Auto Restart Attempts 254L5-04 Fault Reset Interval Time 255o1-07 Second Line Monitor Selection 268o1-08 Third Line Monitor Selection 268u Default Values for Fan and Pump ApplicationsTable 4.11 Fan and Pump Application DefaultsA1-03 SettingParameter 8008 8009 8010 8011A1-02 0: V/f Control 0: V/f Control 0: V/f Control 0: V/f Controlb1-04 – – 1: Reverse Disabled 1: Reverse Disabledb3-05 – – 10.0 s 10.0 sb5-01 – 1: PID Enabled – 1: PID Enabledb5-03 – – – 5.0 sb5-08 – – – 2.00 sb5-13 – – – 2%b5-14 – – – 25.0 sb5-18 – 1: Enabled (b5-19) – 1: Enabled (b5-19)b5-20 – 3: User Set – 3: User Setb5-46 – – – 1: PSIb5-89 – 1: EZ Sleep/Wake Up – 1: EZ Sleep/Wake UpC1-01 – – 90.0 s 60.0 sC1-02 – – 90.0 s 60.0 sC2-01 – – 5.00 s 5.00 sC2-02 – – 5.00 s 5.00 sC2-03 – – 5.00 s 5.00 sC2-04 – – 5.00 s 5.00 sH3-10 – B: PID Feedback B: PID FeedbackL2-01 2: CPU Active 2: CPU Active 2: CPU Active 2: CPU ActiveL3-02 – – 110% 110%L3-06 – – 100% 100%L4-05 – – 0: Stop –L5-04 – – 180.0 s 180.0 sL5-05 1: L5-04 Interval 1: L5-04 Interval 1: L5-04 Interval 1: L5-04 Intervalo1-06 – 1: Selectable – 1: Selectableo1-07 – 102: Output Frequency – 102: Output Frequencyo1-08 – 501: Feedback – 501: Feedback4.6 Application Selection128 YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual