5.6 F: Option Settingsu F4: Analog Monitor Card SettingsThese parameters set the drive for operation with the analog output option card AO-A3. Refer to the instruction manualpackaged with the option card for specific details on installation, wiring, input signal level selection, and parameter setup.n F4-01, F4-03: Terminal V1, V2 Monitor SelectionSelects the data to output from analog terminal V1. Enter the final three digits of Uo-oo to determine which monitor datais output from the option card. Some monitors are only available in certain control modes.No. Parameter Name Setting Range DefaultF4-01 Terminal V1 Monitor Selection 000 to 999 102F4-03 Terminal V2 Monitor Selection 000 to 999 103Note: Set “000” or “031” when using the terminal in through mode. This setting can adjust the V1 and V2 terminal output from PLC viaMEMOBUS/Modbus communications or a communications option.n F4-02, F4-04, F4-05, F4-06: Terminal V1, V2 Monitor Gain and BiasParameters F4-02 and F4-04 determine the gain, while parameters F4-05 and F4-06 set the bias. These parameters are set asa percentage of the output signal from V1 and V2 where 100% equals 10 V output. The terminal output voltage is limited to10 V.No. Parameter Name Setting Range DefaultF4-02 Terminal V1 Monitor Gain -999.9 to 999.9% 100.0%F4-04 Terminal V2 Monitor Gain -999.9 to 999.9% 50.0%F4-05 Terminal V1 Monitor Bias -999.9 to 999.9% 0.0%F4-06 Terminal V2 Monitor Bias -999.9 to 999.9% 0.0%Using Gain and Bias to Adjust Output Signal LevelThe output signal is adjustable while the drive is stopped.Terminal V11. View the value set to F4-02 (Terminal V1 Monitor Gain) on the digital operator. A voltage equal to 100% of theparameter being set in F4-01 will be output from terminal V1.2. Adjust F4-02 viewing the monitor connected to the terminal V1.3. View the value set to F4-05 on the digital operator, terminal V1 will output a voltage equal to 0% of the parameterbeing set in F4-01.4. Adjust F4-05 viewing the output signal on the terminal V1.Terminal V21. View the value set to F4-02 (Terminal V2 Monitor Gain) on the digital operator. A voltage equal to 100% of theparameter being viewed in F4-03 will be output from terminal V2.2. Adjust F4-04 viewing the monitor connected to the terminal V2.3. View the value set to F4-06 on the digital operator, terminal V2 will output a voltage equal to 0% of the parameterbeing set in F4-03.4. Adjust F4-06 viewing the output signal on the terminal V2.n F4-07, F4-08: Terminal V1, V2 Signal LevelSets the output signal level for terminals V1 and V2.No. Parameter Name Setting Range DefaultF4-07 Terminal V1 Signal Level 0, 1 0F4-08 Terminal V2 Signal Level 0, 1 0Setting 0: 0 to 10 V5.6 F: Option Settings198 YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual