Min outputfrequency100%(Max outputfrequency)Output frequencywhen Stop commandwas enteredRun wait time tActive deceleration timeMomentary Power LossMinimum BaseblockTime (L2-03)Figure 5.7 Run Wait Time Depending on Output Frequencyn b1-04: Reverse Operation SelectionEnables and disables Reverse operation. For some applications, reverse motor rotation is not appropriate and may causeproblems (e.g., air handling units, pumps, etc.).No. Parameter Name Setting Range Defaultb1-04 Reverse Operation Selection 0, 1 0Setting 0: Reverse operation enabledPossible to operate the motor in both forward and reverse directions.Setting 1: Reverse operation disabledDrive disregards a Reverse run command or a negative frequency reference.n b1-07: LOCAL/REMOTE Run SelectionThe drive has three separate control sources that can be switched using digital inputs (H1-oo = 1 (LOCAL/REMOTESelection) or 2 (External reference 1/2)) or the LO/RE key on the digital operator. Refer to Setting 1: LOCAL/REMOTESelection on page 206, Refer to Setting 2: External Reference 1/2 Selection on page 207 and Refer to o2-01: LO/RE(LOCAL/REMOTE) Key Function Selection on page 270 for details.• LOCAL: Digital operator. The digital operator sets the frequency reference and Run command.• REMOTE: External reference 1. The frequency reference and Run command source are set by b1-01 and b1-02.• REMOTE: External reference 2. The frequency reference and Run command source are set by b1-15 and b1-16.When switching from LOCAL to REMOTE, or between External reference 1 and External reference 2, the Run commandmay already be present at the location at which the source is being switched. In this case, use parameter b1-07 to determinehow the Run command is treated.No. Parameter Name Setting Range Defaultb1-07 LOCAL/REMOTE Run Selection 0, 1 0Setting 0: Run command must be cycledWhen the Run command source differs between the old source and the new source (e.g., the old source was the terminals andthe new source is serial communication), and the Run command is active at the new source as the switchover occurs, the drivewill not start or the drive will stop operation if it was previously running. The Run command must be cycled at the new sourceto restart the drive.Setting 1: Accept Run command at the new sourceWhen the Run command is active at the new source, the drive starts or continues operation if it was previously running.WARNING! Sudden Movement Hazard. The drive may start unexpectedly if switching control sources when b1-07 = 1. Clear all personnelfrom rotating machinery and electrical connections prior to switching control sources. Failure to comply may cause death or serious injury.n b1-08: Run Command Selection while in Programming ModeAs a safety precaution, the drive will not normally respond to a Run command input when the digital operator is being usedto adjust parameters in Programming Mode (Verify Menu, Setup Mode, Parameter Settings Mode, and Auto-Tuning Mode).If required by the application, set b1-08 to allow the drive to run while in Programming Mode.No. Parameter Name Setting Range Defaultb1-08 Run Command Selection while in Programming Mode 0 to 2 05.2 b: ApplicationYASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual 1515 Parameter Details