S3-13PI2 Low FeedbackDetection LevelPI2 Feedback(U5-18)S3-15PI2 High FeedbackDetection LevelOn-delayTimerOn-delayTimerS3-16PI2 High FeedbackDetection TimeS3-14PI2 Low FeedbackDetection TimePI2 disabledS3-17 = 0FalseTrueFalseTrueMulti-function outputH2-oo = 71PI2 Feedback LowMulti-function outputH2-oo = 72PI2 Feedback High+-+-Figure 5.95 PI Low Feedback Detection Leveln S3-14: Secondary PI Low Feedback Detection TimeSets the secondary PI low feedback detection delay time in seconds.No. Name Setting Range DefaultS3-14 Secondary PI Low Feedback Detection Time 0.0 to 25.5 s 1.0 sn S3-15: Secondary PI High Feedback LevelSets the secondary PI high feedback detection level.No. Name Setting Range DefaultS3-15 Secondary PI High Feedback Level 0.00 to 600.00 <1> 300.0 <2><1> Upper limit is S3-02, decimal place holder is determined by S3-03.<2> Unit is determined by S3-04.n S3-16: Secondary PI High Feedback Detection TimeSets the secondary PI high feedback detection delay time in seconds.No. Name Setting Range DefaultS3-16 Secondary PI High Feedback Detection Time 0.0 to 25.5 s 1.0 sn S3-17: Secondary PI Feedback Detection SelectionSelects when secondary PI controller low and high feedback detection is active.No. Name Setting Range DefaultS3-17 Secondary PI Feedback Detection Selection 0 or 1 0Setting 0: Secondary PI EnabledSetting 1: Alwaysu S6: P1000 Protectionn S6-01: Emergency Override SpeedSets the sped command used in emergency override mode when S6-02 = 0.No. Name Setting Range DefaultS6-01 Emergency Override Speed 0.00 to 240.00 Hz 0.00 Hzn S6-02: Emergency Override Reference SelectionSelects the emergency override speed source.5.11 S: Special Application284 YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual